Cable Current Ratings

Current carrying capacity (Iz) for common cable types by installation method

BS 7671:2018+A2:2022 Tables 4D1A-4J1

Important: These are tabulated values (It)

Apply correction factors for ambient temperature (Ca), grouping (Cg), and thermal insulation (Ci) as required. The installed current rating is: Iz = It × Ca × Cg × Ci

Twin & Earth (6242Y)

Flat twin and earth cable with PVC insulation

Reference: Table 4D5 | Max temp: 70°C

Size (mm²)
Clipped Direct
Conduit in Wall
Conduit in Ceiling
In Trunking
On Cable Tray
115.513.51313.515.5
1.52017.516.517.520
2.52724232427
43732303237
64741384147
106457525764
168576697685
Singles in Conduit/Trunking

Single core PVC cables (6491X) in conduit or trunking

Reference: Table 4D1A | Max temp: 70°C

Size (mm²)
Clipped Direct
Conduit in Wall
Conduit in Ceiling
In Trunking
On Cable Tray
Free Air
115.513.51313.516.519
1.52017.516.517.52224
2.5272423243033
4373230324045
6474138415158
10655752577080
168776697694107
2511410190101119138
35141125111125148171
50182151133151180209
70234192168192232269
95284232201232282328
120330269232269328382
SWA PVC (BS 5467)

Steel wire armoured cable with PVC insulation

Reference: Table 4D4A | Max temp: 70°C

Size (mm²)
Clipped Direct
Buried Direct
On Cable Tray
Free Air
1.521272126
2.528362835
437463745
647574757
1064766478
16849884102
25110125110133
35134151134163
50161179161196
70200219200243
95241262241293
120278299278338
150313335313380
185354377354430
240410434410498
300463488463563
SWA XLPE (BS 5467)

Steel wire armoured cable with XLPE insulation

Reference: Table 4E4A | Max temp: 90°C

Size (mm²)
Clipped Direct
Buried Direct
On Cable Tray
Free Air
1.525322531
2.534423442
444534455
657675770
1077897795
16102116102125
25133148133163
35163178163200
50196211196240
70244258244299
95296307296363
120343351343420
150387393387474
185440442440540
240514509514631
300583572583716
Mineral Insulated (MICC)

Mineral insulated copper clad cable

Reference: Table 4J1 | Max temp: 105°C

Size (mm²)
Clipped Direct
Conduit in Wall
Free Air
1231827
1.5282333
2.5383144
4504057
6625171
10826894
1610689121
25135115155
Flexible Cable (H05VV-F)

PVC flexible cord for appliance connections

Reference: Table 4D3A | Max temp: 70°C

Size (mm²)
Clipped Direct
Free Air
0.533
0.7566
11010
1.51316
2.51825
42332
H07RN-F (Heavy Rubber Flex)

Heavy duty rubber flexible cable

Reference: Table 4D3A | Max temp: 60°C

Size (mm²)
Clipped Direct
Free Air
11417
1.51822
2.52530
43340
64352
106072
168096
25106127
35131157
50159190
70202242
95245294
120284340

Notes

  • • Values are for copper conductors. Aluminium has lower ratings.
  • • Reference ambient temperature is 30°C (25°C for buried cables).
  • • Single-phase values shown. Three-phase may differ slightly.
  • • Always verify against the full BS 7671 tables for critical applications.

Installation Method Key

Clipped Direct - Clipped direct to surface or on tray (Reference Method C)
Conduit in Wall - Enclosed in conduit on a wall (Reference Method B)
Conduit in Ceiling - Enclosed in conduit in thermally insulated ceiling
In Trunking - Enclosed in trunking
On Cable Tray - On perforated cable tray (Reference Method E/F)
Buried Direct - Buried direct in ground
Free Air - In free air with spacing