Skip to content

Consumer Unit Regulations (Amd 3)

Amendment 3 consumer unit requirements — metal enclosures, AFDD, SPD, and circuit arrangement

Metal CUAFDDSPDDual RCD

Metal Consumer Unit Requirement

Amendment 3 to BS 7671 mandates non-combustible enclosures for consumer units in domestic premises, primarily to reduce the risk of fire.

Regulation 421.1.201 requires that in domestic (household) premises, a consumer unit or similar switchgear assembly must be enclosed in a non-combustible enclosure — in practice, this means a steel consumer unit. Plastic consumer units can no longer be installed in domestic premises. This applies to new installations and when an existing consumer unit is replaced.

Replacement Trigger

When replacing a consumer unit — even a like-for-like upgrade — the installation must be brought up to current standards. This includes 30mA RCD protection on all circuits, metal enclosure, correct labelling, and Part P notification.

Consumer Unit Configurations

CU configuration comparison

BS 7671 and manufacturer guidance
ConfigurationDescriptionProsCons
Split-load (dual RCD)Two 63A RCDs each protecting half the circuitsLowest costHalf circuits lost on RCD trip
High integrityTwo RCDs + main switch, with some circuits on non-RCD waysFlexibilitySome circuits may lack RCD protection
Full RCBOIndividual RCBO per circuitBest discriminationHigher cost per way
Main switch onlyMain switch + RCBOs on every wayMaximum flexibilityHighest cost

Full RCBO boards are now the preferred configuration for new domestic installations.

RCD and RCBO Requirements

BS 7671 requires 30mA RCD protection for socket outlets up to 32A, mobile equipment up to 32A outdoors, cables installed in walls at less than 50mm depth without mechanical protection, and all circuits in domestic installations (with limited exceptions).

RCBO type selection guidance

BS 7671 Regulation 531.3
Circuit TypeRCBO TypeReason
General sockets, lightingType ADetects AC and pulsating DC faults
EV chargerType A (+ Type B RDC-DD)DC fault current from charger electronics
Cooker (induction hob)Type A or Type FHigh-frequency leakage from induction
VFD / inverter circuitsType BDetects smooth DC fault currents
Fire alarmType AC (if required)Keep simple — avoid nuisance trips

SPD and AFDD Provisions

SPD Installation

Fit a Type 2 SPD at the consumer unit origin to protect against transient overvoltages. Where the installation has an external lightning protection system, a coordinated Type 1 + Type 2 arrangement is required. SPDs need a dedicated MCB (typically 40A Type B) and a short cable run to the main earth bar.

AFDD Considerations

AFDDs detect series and parallel arc faults that RCDs and MCBs cannot. They are recommended for final circuits in locations with sleeping accommodation, HMOs, and timber-framed buildings. When specifying AFDDs, ensure the consumer unit has sufficient space — AFDD/RCBO combination devices are typically double-width modules.

A typical modern 3-bed house requires a minimum 12-way consumer unit: 2 x ring final or radial sockets, 2 x lighting, cooker, shower, immersion, smoke alarm, outdoor circuit, and spare ways for future additions. Always include at least two spare ways.

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch