Correction Factors

Derating factors for cable current carrying capacity

BS 7671:2018+A2:2022 Tables 4B1, 4C1

How to Apply Correction Factors

The installed current rating is calculated as: Iz = It × Ca × Cg × Ci

  • It = Tabulated current rating
  • Ca = Ambient temperature correction factor
  • Cg = Grouping correction factor
  • Ci = Thermal insulation correction factor (if applicable)
Ambient Temperature Correction Factor (Ca)

BS 7671 Table 4B1 - For cables not in ground (reference 30°C)

Ambient Temp (°C)
PVC (70°C)
Twin & Earth, SWA PVC
XLPE (90°C)
SWA XLPE
251.031.02
30(reference)1.001.00
350.940.96
400.870.91
450.790.87
500.710.82
550.610.76
600.500.71
65-0.65
70-0.58
Grouping Correction Factor (Cg)

BS 7671 Table 4C1 - For cables bunched together or in enclosed spaces

Number of Circuits/CablesCorrection Factor (Cg)Effective Capacity
1(no derating)1.00100%
20.8080%
30.7070%
40.6565%
50.6060%
60.5757%
70.5454%
80.5252%
90.5050%
120.4545%
160.4141%
20 or more0.3838%
Thermal Insulation Correction Factor (Ci)

BS 7671 Table 52.2 - For cables surrounded by thermal insulation

Length in InsulationCorrection Factor (Ci)
50mm or less0.89
51mm to 100mm0.81
101mm to 200mm0.68
201mm to 400mm0.55
Over 400mm0.50
Ground Temperature Correction (Buried Cables)

BS 7671 Table 4B3 - Reference ground temperature 20°C

Ground Temp (°C)PVC (70°C)XLPE (90°C)
101.101.07
151.051.04
20(reference)1.001.00
250.950.96
300.890.93
350.840.89
400.770.85
Soil Thermal Resistivity (Buried Cables)

BS 7671 Table 4B4 - Reference resistivity 2.5 K·m/W

Soil Resistivity (K·m/W)Soil TypeCorrection Factor
1.0Very wet soil, water-logged1.18
1.5Wet soil1.10
2.5Damp soil(reference)1.00
3.0Dry soil0.96

Important Notes

  • Multiple Factors: When more than one correction factor applies, multiply them together: Ca × Cg × Ci
  • Significant Derating: If total correction factor is below 0.7, consider revising the installation design.
  • Interpolation: For intermediate values, use the next lower factor (conservative approach).
  • Different Circuits: When grouping circuits with different load types, consider whether they operate simultaneously.
  • Enclosed Trunking: Cables in totally enclosed trunking require additional derating beyond these tables.