Earthing & Bonding Requirements
Complete earthing and bonding guide — TN-S, TN-C-S, TT systems, CPC sizing, and bonding conductors
Earthing Systems Explained
BS 7671 recognises three main earthing arrangements for UK supplies. The system type determines your Ze value, CPC sizing, and bonding requirements.
UK earthing system characteristics
BS 7671 Part 3, Reg 411.4| System | Earth Path | Typical Ze | Notes |
|---|---|---|---|
| TN-S | Supply cable sheath | 0.8 ohms max | Older supplies, separate earth conductor |
| TN-C-S (PME) | Combined neutral/earth | 0.35 ohms max | Most common modern supply |
| TT | Local earth electrode | Up to 200 ohms | RCD protection mandatory |
Ze is measured at the origin with all installation earthing disconnected.
TT Systems Require RCDs
CPC Sizing — Table 54.7 and Adiabatic Equation
The circuit protective conductor must withstand fault energy without exceeding its thermal limit.
Minimum CPC size by line conductor cross-section
BS 7671 Table 54.7| Line Conductor S (mm²) | Minimum CPC (mm²) |
|---|---|
| S <= 16 | Same as line conductor |
| 16 < S <= 35 | 16 |
| S > 35 | S / 2 |
These are minimum values. Where the CPC is not the same material as the line conductor, apply correction per Regulation 543.1.3.
S = sqrt(I²t) / k- S
- = Minimum CPC cross-sectional area (mm²)
- I²t
- = Energy let-through of the protective device (A²s)
- k
- = Factor from Table 54.4 (e.g. 115 for copper/PVC)
BS 7671 Regulation 543.1.3
Main Protective Bonding
Main bonding connects extraneous conductive parts to the MET to prevent dangerous potential differences during a fault.
Minimum main bonding conductor sizes
BS 7671 Table 54.8| Supply Type | Min. Bonding Conductor | Services Bonded |
|---|---|---|
| TN-S | 6mm² Cu | Gas, water, oil, structural steel |
| TN-C-S (PME) | 10mm² Cu | Gas, water, oil, structural steel |
| TT | 6mm² Cu | Gas, water, oil, structural steel |
Plastic Service Entries
Supplementary Bonding
Supplementary bonding connects exposed conductive parts and extraneous conductive parts within a location to limit touch voltage. For bathrooms, conductors of 4mm² (mechanically protected) or 2.5mm² (where the connection is made using a BS EN 60998 connector and is protected) are typical.
When You Can Omit Bathroom Bonding