Skip to content

Motor Starters & Control Circuits

Guide to DOL, star-delta, soft starters, and VFDs with wiring diagrams and selection criteria

DOLStar-deltaSoft starterVFD

Motor Full Load Current

Calculating the full load current from the motor nameplate data is the starting point for cable sizing, protection, and starter selection.

IL = P / (sqrt(3) x VL x eta x cos(phi))
IL
= Full load line current (A)
P
= Motor rated power (W)
VL
= Line voltage, typically 400V
eta
= Motor efficiency (e.g. 0.88)
cos(phi)
= Power factor (e.g. 0.85)

Motor nameplate data

Example: A 7.5kW motor, efficiency 0.88, power factor 0.85 at 400V draws 7500 / (1.732 x 400 x 0.88 x 0.85) = 14.5A full load current.

Starting Methods Comparison

Motor starting method characteristics

General motor starting guidance
Starter TypeStarting CurrentStarting TorqueTypical Use
DOL6-8x FLC100% ratedUp to 7.5kW (depends on supply)
Star-Delta2-3x FLC33% rated7.5kW - 75kW, light start loads
Soft Starter2-4x FLCAdjustablePumps, conveyors, compressors
VFD1-1.5x FLCAdjustable 0-150%Speed control, energy saving

FLC = Full Load Current. Starting current is the peak inrush during acceleration.

Supply Capacity

DNOs typically limit motor starting current to avoid voltage disturbance on the network. Check the supply capacity before specifying DOL starting for motors above 5.5kW. A VFD or soft starter may be required by the DNO.

MCB and Protection Selection

MCB type selection for motor circuits

BS 7671 and BS EN 60898
MCB TypeTrip RangeMotor Application
Type B3-5x InNot suitable for motor circuits
Type C5-10x InDOL starters, soft starters, VFDs
Type D10-20x InStar-delta transition, high inertia loads

Motor circuits require both short-circuit protection (MCB/MCCB) and overload protection (thermal or electronic overload relay). The overload is set to the motor FLC and trips on sustained overcurrent. The MCB handles fault current only.

VFD Cable Considerations

EMC and Cable Selection

VFDs produce high-frequency switching noise that can cause electromagnetic interference. Use screened motor cable (e.g. SY or CY cable) between the VFD and motor. Keep VFD output cables separated from signal and data cables by at least 300mm. The cable screen must be bonded at both ends.

Cable Derating with VFDs

VFD output waveforms contain harmonics that increase cable heating. Some manufacturers recommend derating cables by 5-10% when fed from a VFD. Check the VFD manual for specific cable sizing guidance.

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch