Skip to content

Protection Coordination & Discrimination

Overcurrent protection coordination — discrimination, back-up protection, and cascading

DiscriminationBack-upCascadingTime-current

Disconnection Times

BS 7671 requires fault disconnection within specified times to limit the duration of touch voltage during an earth fault.

Maximum disconnection times for TN systems

BS 7671 Table 41.1
Circuit TypeUo (V)Max Time (s)Regulation
Final circuit (socket outlets)2300.4411.3.2.2
Final circuit (fixed equipment)2300.4411.3.2.2
Distribution circuit2305411.3.2.3
Special locations (e.g. bathroom)2300.4701.411.3.2

For TT systems, the same disconnection times apply but are typically achieved by RCD operation.

Verifying Disconnection

Disconnection time is verified by comparing the measured Zs against the maximum Zs values in Tables 41.2 to 41.4 of BS 7671. If the measured Zs exceeds the tabulated maximum, the device cannot disconnect within the required time and an RCD or supplementary bonding is needed.

Time-Current Characteristics

Each protective device type has a distinct operating curve that determines how quickly it trips at different fault currents.

MCB instantaneous trip ranges

BS EN 60898
MCB TypeMagnetic Trip RangeTypical Use
Type B3-5 x InDomestic, resistive loads
Type C5-10 x InSmall motors, fluorescent lighting
Type D10-20 x InLarge motors, transformers, X-ray

In = rated current of the MCB.

BS 88 fuses have inverse time-current characteristics — higher fault currents result in faster clearance. Unlike MCBs, fuses do not have a fixed magnetic trip threshold, making them inherently better at providing discrimination when devices are rated in a 2:1 ratio.

Discrimination Ratios

Typical discrimination ratios for full selectivity

Manufacturer discrimination tables
Upstream DeviceDownstream DeviceRatio Required
BS 88 FuseBS 88 Fuse2:1
BS 88 FuseMCB Type B~1.6:1
MCB Type BMCB Type B2:1 (limited range)
MCB Type CMCB Type BCheck curves
MCCBMCBManufacturer data

Full discrimination up to maximum fault level is only guaranteed when confirmed by the manufacturer.

Use Fuses for Critical Discrimination

Where loss of supply to other circuits is unacceptable (e.g. hospital boards, process plant), use BS 88 fuses at distribution level. Their predictable time-current curves make achieving discrimination straightforward.

Back-Up Protection (Cascading)

Back-up protection allows a device with a lower breaking capacity to be installed where the prospective fault current (Ipf) exceeds its rated breaking capacity, provided a suitable upstream device limits the energy let-through. This must be verified using the manufacturer's published cascading tables.

I²t (let-through) of upstream <= I²t (withstand) of downstream
I²t
= Energy let-through in A²s during the fault

BS 7671 Regulation 434.5.1

Cascading Is Manufacturer-Specific

Back-up protection combinations are only valid when tested and published by the device manufacturer. You cannot assume an untested combination will provide adequate protection — always check the specific product data.

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch