Skip to content

Motor Circuit Calculator

Cable sizing and protection for motor circuits

Reference Info & Formulas
Starting Methods

DOL: 6× FLC, simple

Star-Delta: 2× FLC, reduced torque

Soft Starter: 3× FLC, smooth

VFD: 1.5× FLC, best control

Key Points

• Cable sized for 1.25× FLC

• Type D MCB for DOL start

• Overload at 1.05× FLC

BS 7671 Section 552

Motor Details
Enter motor specifications
Installation
Cable run details
m

Data: BS 7671:2018+A2:2022 — Section 552, Appendix 4

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

Motor circuit design sizes cable to full load current, selects a starter type, and coordinates overload and short-circuit protection.

Unlike most circuits where cable is sized to the protective device rating, motor circuits use a split protection approach. The cable is sized to the motor's full load current (FLC), and a thermal overload relay set at or near FLC protects against sustained overcurrent. The MCB or fuses provide short-circuit protection only.

Starting current for DOL motors is typically 6-8 times FLC, lasting 2-10 seconds depending on motor size and load inertia. The protective devices must be coordinated so the starting transient does not cause nuisance tripping, while genuine faults are still cleared rapidly.

Quick Reference — Starting Methods

Motor starting methods and their characteristics

BS 7671 Section 552
Starting MethodStarting CurrentStarting TorqueNotes
DOL (Direct On Line)6-8× FLC100% ratedSimple, high inrush, up to ~5.5kW typical
Star-Delta2-3× FLC33% ratedReduced torque, requires 6 cables to motor
Soft Starter2-4× FLCVariableSmooth ramp, reduced mechanical stress
VFD (Variable Frequency Drive)1-1.5× FLCFull at all speedsFull speed control, generates harmonics

Starting current multiples are approximate and depend on motor design and connected load.

Protection Coordination

Motor circuit protection requires coordination between two devices: the short-circuit protective device (MCB or fuses at the distribution board) and the thermal overload relay (at the motor starter). The MCB is rated above the starting current to avoid nuisance tripping, while the overload relay is set at or near FLC to protect against sustained overcurrent.

This split approach means the cable only needs to be sized for the motor FLC rather than the MCB rating, reducing cable costs on larger motor circuits. The overload relay acts as the cable's running protection.

Practical Notes

Type D MCBs for Motor Circuits

Type D MCBs trip at 10-20 times rated current, allowing them to ride through the 6-8× FLC starting transient of a DOL motor. Type B (3-5×) will nuisance trip on every start. Type C (5-10×) is marginal and should only be used with reduced-inrush starters such as soft starters or VFDs.

Star-Delta Overload Setting

For Star-Delta starters, set the thermal overload relay to 58% of the motor's full load current. During normal running in delta configuration, the phase current through the overload is 1/√3 (0.577) times the line current. Setting the relay to the full FLC would leave the motor unprotected against overload.

VFD Harmonic Considerations

Variable frequency drives generate harmonics that can affect sensitive equipment on the same supply. For installations above 15kW, consider line reactors or harmonic filters. Third-order harmonics are particularly problematic on three-phase supplies as they sum in the neutral conductor (Regulation 523.6.3).

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch