Circuit Breaker / RCBO Selector
Select the correct MCB type and rating for any circuit
Reference Info & Formulas
Type B: Trips at 3-5x In. General purpose.
Type C: Trips at 5-10x In. Motors, transformers.
Type D: Trips at 10-20x In. High inrush loads.
Ib ≤ In ≤ Iz
Design current ≤ MCB rating ≤ Cable rating
Reg 433.1.1
Data: BS 7671:2018+A2:2022, BS EN 60898-1
For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.
How This Calculator Works
Circuit breaker selection coordinates the protective device with both the load current and the cable's current-carrying capacity.
The calculator applies the fundamental coordination rule from BS 7671 Regulation 433.1. The protective device rating must sit between the circuit's design current and the cable's corrected current-carrying capacity, ensuring the cable is never subjected to currents beyond its thermal limit.
Ib ≤ In ≤ Iz- Ib
- = Design current of the circuit (A)
- In
- = Rated current of the protective device (A)
- Iz
- = Current-carrying capacity of the cable (A), after correction factors
BS 7671 Regulation 433.1
The calculator also checks that the maximum earth fault loop impedance (Zs) for the selected device does not exceed the tabulated values in Tables 41.2 to 41.4, ensuring automatic disconnection of supply within the required time.
Quick Reference — MCB Trip Characteristics
MCB types and their magnetic trip ranges
BS EN 60898-1| MCB Type | Trip Range (× In) | Typical Applications |
|---|---|---|
| Type B | 3–5 | Domestic circuits, resistive loads, socket outlets, lighting |
| Type C | 5–10 | Small motors, fluorescent/LED lighting banks, air conditioning |
| Type D | 10–20 | Large motors, transformers, welding equipment, X-ray machines |
The lower value is the minimum current at which the device must trip instantaneously. Below this range, the thermal element provides delayed tripping.
Quick Reference — RCD Requirements
30mA RCD protection requirements under Amendment 2
BS 7671:2018+A2:2022| Circuit Type | RCD Required? | Regulation |
|---|---|---|
| Socket outlets ≤ 32A | Yes | 411.3.4 |
| Bathroom / shower room circuits | Yes | 701.411.3.3 |
| Outdoor circuits / mobile equipment | Yes | 411.3.4 |
| Cables concealed in walls < 50mm deep | Yes | 522.6.202 |
| Domestic lighting circuits | Yes | 411.3.4 |
| Fire alarm / emergency lighting | May be exempt | See 411.3.5 |
Practical Notes
Maximum Zs Must Be Verified
RCBO Boards Improve Selectivity
Type B Is Default for Domestic
Frequently Asked Questions
SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.