Skip to content

Circuit Breaker / RCBO Selector

Select the correct MCB type and rating for any circuit

Reference Info & Formulas
MCB Types

Type B: Trips at 3-5x In. General purpose.

Type C: Trips at 5-10x In. Motors, transformers.

Type D: Trips at 10-20x In. High inrush loads.

Key Rule

Ib ≤ In ≤ Iz

Design current ≤ MCB rating ≤ Cable rating

Reg 433.1.1

Circuit Details
What is the circuit for?
Additional Factors
Any special considerations?

Data: BS 7671:2018+A2:2022, BS EN 60898-1

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

Circuit breaker selection coordinates the protective device with both the load current and the cable's current-carrying capacity.

The calculator applies the fundamental coordination rule from BS 7671 Regulation 433.1. The protective device rating must sit between the circuit's design current and the cable's corrected current-carrying capacity, ensuring the cable is never subjected to currents beyond its thermal limit.

Ib ≤ In ≤ Iz
Ib
= Design current of the circuit (A)
In
= Rated current of the protective device (A)
Iz
= Current-carrying capacity of the cable (A), after correction factors

BS 7671 Regulation 433.1

The calculator also checks that the maximum earth fault loop impedance (Zs) for the selected device does not exceed the tabulated values in Tables 41.2 to 41.4, ensuring automatic disconnection of supply within the required time.

Quick Reference — MCB Trip Characteristics

MCB types and their magnetic trip ranges

BS EN 60898-1
MCB TypeTrip Range (× In)Typical Applications
Type B3–5Domestic circuits, resistive loads, socket outlets, lighting
Type C5–10Small motors, fluorescent/LED lighting banks, air conditioning
Type D10–20Large motors, transformers, welding equipment, X-ray machines

The lower value is the minimum current at which the device must trip instantaneously. Below this range, the thermal element provides delayed tripping.

Quick Reference — RCD Requirements

30mA RCD protection requirements under Amendment 2

BS 7671:2018+A2:2022
Circuit TypeRCD Required?Regulation
Socket outlets ≤ 32AYes411.3.4
Bathroom / shower room circuitsYes701.411.3.3
Outdoor circuits / mobile equipmentYes411.3.4
Cables concealed in walls < 50mm deepYes522.6.202
Domestic lighting circuitsYes411.3.4
Fire alarm / emergency lightingMay be exemptSee 411.3.5

Practical Notes

Maximum Zs Must Be Verified

Selecting the correct MCB type and rating is not enough — you must also confirm that the earth fault loop impedance (Zs) at the furthest point of the circuit does not exceed the maximum value for the device. If Zs is too high, the MCB will not disconnect within the required 0.4s (or 5s for distribution circuits), creating a shock hazard. Refer to Tables 41.2 (BS 88 fuses), 41.3 (BS 3036 fuses), and 41.4 (BS EN 60898 MCBs).

RCBO Boards Improve Selectivity

Where budget permits, specify an RCBO board rather than a split-load consumer unit. Each circuit gets independent earth fault protection, so a single fault does not take out an entire RCD group. This is particularly valuable in HMOs, commercial premises, and any installation where loss of multiple circuits is unacceptable.

Type B Is Default for Domestic

Unless there is a specific reason to use Type C or D (motor loads, large inductive lighting arrays), always default to Type B MCBs for domestic circuits. Type B devices have lower magnetic trip thresholds, meaning they tolerate higher Zs values and provide faster disconnection at lower fault currents — important for longer cable runs and TT systems.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch