Max Zs Calculator
Maximum earth fault loop impedance values for protective devices
Reference Info & Formulas
When testing, measured Zs should be ≤80% of the tabulated value.
This accounts for conductor resistance increasing at operating temperature (up to 80°C under fault conditions).
BS 7671 Regulation 411.4.4
Type B
3-5× In. Standard circuits.
Type C
5-10× In. Motor/inductive loads.
Type D
10-20× In. Transformers, welders.
Recommended kit
As an Amazon Associate we earn from qualifying purchases.

Socket & See SOK32 Professional Socket Tester, Green

Circuit Tester, 6V/12V/24V Test Light Automotive Truck Car Electrical Circuit Continuity Tester Test Light Indicator with Pen Tool Electrical System Tester

Eightwood Pen Electric Tester Mains Tester Screwdriver Electrical Screwdriver 220V Voltage Electrical Pen 220V Voltage Electric with Test Power Detector Probe

Voltage Tester Pen, 90V-1000V Non Contact Voltage Tester Pen Voltage Detector Pen Volt Stick with LED Flashlight and Buzzer Alarm Live Wire Detector Pen Adjustable Sensitivity (No battery)

Martindale PD690S-C 690V AC Proving Unit with TC71 Soft Carry Case,Yellow

Martindale CP520 Socket Tester with Earth Test Point
Data: BS 7671:2018+A2:2022 — Tables 41.2–41.4, Appendix 14
For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.
How This Calculator Works
Earth fault loop impedance Zs determines whether a protective device will disconnect fast enough to prevent electric shock.
The total earth fault loop impedance is the sum of the external loop impedance Ze (from the supply transformer to your intake) and the internal impedance of the circuit conductors (R1 + R2). This value must not exceed the maximum listed in BS 7671 Tables 41.2 to 41.4 for the specific protective device type and rating.
Zs = Ze + (R1 + R2)- Ze
- = External earth fault loop impedance (measured at intake)
- R1
- = Resistance of the line conductor
- R2
- = Resistance of the circuit protective conductor (CPC)
BS 7671 Regulation 411.4.5
When verifying an installation, the measured Zs at ambient temperature must be no greater than 80% of the tabulated maximum value. This accounts for the increase in conductor resistance when the cable reaches its normal operating temperature under fault conditions.
Quick Reference — Maximum Zs for Type B MCBs
Maximum earth fault loop impedance (Type B MCBs to BS EN 60898)
Table 41.3 (with 0.95 Cmin applied)| MCB Rating (A) | Max Zs (Ω) | 80% Value (Ω) |
|---|---|---|
| 6 | 7.67 | 6.14 |
| 10 | 4.6 | 3.68 |
| 16 | 2.87 | 2.3 |
| 20 | 2.3 | 1.84 |
| 32 | 1.44 | 1.15 |
| 40 | 1.15 | 0.92 |
| 50 | 0.92 | 0.74 |
80% values are the maximum acceptable measured Zs at ambient temperature (approximately 20°C).
Quick Lookup by Device
Practical Notes
The 80% Rule Is Not Optional
Borderline Readings
Beware of Parallel Earth Paths
Frequently Asked Questions
SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.