Max Zs for 32A Type D MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
0.34Ω
Testing Limit
0.27Ω
Max Zs (5s)
0.68Ω
Ia (0.4s)
640A
At a Glance
- Device
- MCB Type D — 32A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 0.34Ω
- Max Zs (5s)
- 0.68Ω
- Testing Limit (80%)
- 0.27Ω
- Ia (0.4s)
- 640A
About MCB Type D
Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.
Typical Circuits for 32A Type D MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Large transformer | 6.0mm² | Isolation / auto transformer circuits |
Worked Example: Maximum Cable Run for 32A MCB Type D
- Maximum Zs (tabulated) = 0.34Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 0.34 × 0.8 = 0.27Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 0.27 − 0.35 = —Ω
- Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
- The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.
The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.
0.4s vs 5s Disconnection — Significant Difference for Type D
Type D MCBs require 20× In for 0.4s but only 10× In for 5s. At 32A: max Zs = 0.34Ω (0.4s) vs 0.68Ω (5s). The 5s value is exactly double. This is why Type D MCBs are mainly used on distribution circuits where 5s disconnection is acceptable.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 0.34Ω | 0.27Ω |
| 5 seconds | 0.68Ω | 0.54Ω |
32A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 1.37Ω | 1.1Ω |
| MCB Type C | 0.68Ω | 0.54Ω |
| MCB Type D | 0.34Ω | 0.27Ω |
| BS 88 Fuse | 1.04Ω | 0.83Ω |