Skip to content

R1+R2 Calculator

Calculate combined line & CPC resistance, Zs, and verify BS 7671 compliance

Reference Info & Formulas
What is R1+R2?

R1 = line conductor resistance

R2 = CPC (earth) resistance

Measured during dead testing at the furthest point of the circuit.

Zs = Ze + (R1 + R2)

80% Rule

BS 7671 table values assume conductors at 70°C. On-site tests are at ~20°C.

Multiply table Zs by 0.8 to get the field testing limit.

Cable Details
Select cable type and enter run length
Supply & Protection
Enter Ze and protective device details

Data: BS 7671:2018+A2:2022 — IET On-Site Guide Table 11, Tables 41.2–41.4

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

R1+R2 is the combined resistance of the line conductor and circuit protective conductor, measured as a dead test to verify continuity.

R1 is the resistance of the line conductor and R2 is the resistance of the CPC. Their sum is calculated from conductor resistance per metre tables at 20°C. For example, 2.5mm² line with 1.5mm² CPC gives 7.41 + 12.10 = 19.51 mΩ/m. This value feeds directly into the earth fault loop impedance calculation.

Zs = Ze + (R1 + R2)
Zs
= Total earth fault loop impedance (Ω)
Ze
= External earth fault loop impedance (Ω)
R1
= Line conductor resistance (Ω)
R2
= CPC resistance (Ω)

BS 7671 Regulation 411.4.5

Quick Reference — R1+R2 Per Metre at 20°C

Common T&E combinations — conductor resistance per metre

IET On-Site Guide Table B1
Cable (Line/CPC mm²)R1+R2 (mΩ/m)
1.5 / 1.030.2
2.5 / 1.519.51
4.0 / 1.516.71
6.0 / 2.510.49
10.0 / 4.06.44
16.0 / 6.04.23

Values are at 20°C. Measured resistance will vary with ambient temperature.

Practical Notes

Dead Test Only

R1+R2 must come from a dead test using a low-resistance ohmmeter. You cannot derive it from a live Zs reading because parallel earth paths through bonding and other circuits reduce the measured value, giving a misleadingly low figure.

Null Your Test Leads

Always null (zero) your test leads before measuring. Lead resistance of around 0.05Ω per metre adds directly to your reading, which can push a borderline result over the maximum Zs limit.

Ring Circuit Readings

For ring final circuits, readings vary across socket outlets due to the parallel resistance mathematics of the figure-of-eight test. The highest reading recorded at any socket is the circuit's R1+R2 value.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch