Skip to content

Disconnection Time Calculator

Verify ADS compliance — check if your protective device will disconnect in time

Reference Info & Formulas
Max Disconnection Times

TN systems:

Final circuit: 0.4 s

Distribution: 5.0 s

TT systems:

Final circuit: 0.2 s

Distribution: 1.0 s

BS 7671 Table 41.1

MCB Trip Multipliers

Type B: 3–5 × In

Type C: 5–10 × In

Type D: 10–20 × In

Protective Device
Select the device protecting the circuit
Circuit Details
Enter measured Zs and earthing system

Data: BS 7671:2018+A2:2022 — Table 41.1, Tables 41.2–41.4

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

Automatic Disconnection of Supply (ADS) ensures protective devices clear faults within the time limits set by BS 7671.

The calculator compares the prospective fault current against the operating characteristics of the protective device. Fault current is derived from the earth fault loop impedance: If = 0.95 × U₀ / Zs. This value must exceed the device's instantaneous trip threshold to achieve disconnection within the required time.

If = 0.95 × U₀ / Zs
If
= Prospective earth fault current (A)
U₀
= Nominal line-to-earth voltage (230V)
Zs
= Earth fault loop impedance (Ω)
0.95
= Factor for voltage tolerance at origin

BS 7671 Regulation 411.4.5

Maximum Disconnection Times

Required disconnection times by system and circuit type

BS 7671 Table 41.1
SystemCircuit TypeMax Time (s)
TNFinal ≤63A (socket outlets)0.4
TNFinal ≤63A (fixed equipment)0.4
TNDistribution circuits5
TTFinal circuits0.2
TTDistribution circuits1

MCB Magnetic Trip Multiples

Instantaneous trip current ranges by MCB type

BS EN 60898
MCB TypeTrip Range (× In)Typical Use
Type B3–5Domestic, resistive loads
Type C5–10Small motors, fluorescent lighting
Type D10–20Large motors, transformers, X-ray equipment

The lower bound is the minimum current for guaranteed instantaneous trip.

Practical Notes

18th Edition Change

Final circuits rated up to 63A that include socket outlets now require 0.4s disconnection in TN systems. Previously, circuits above 32A were commonly treated as distribution circuits with a 5s allowance. This affects cooker circuits with a socket outlet.

Type B MCBs for Higher Zs

Type B MCBs have lower magnetic trip thresholds, allowing higher permissible Zs values. They are better suited for longer cable runs or TT installations where fault levels are lower.

Exceeding Maximum Zs

If measured Zs exceeds the tabulated maximum for the protective device, the device may not disconnect within the required time. This is classified as a C1 (danger present) defect on an EICR and requires immediate remedial action.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch