Skip to content

Fault Current Calculator

Calculate prospective fault current (PFC) for protective device selection

Reference Info & Formulas
What is PFC?

PSCC - Prospective Short Circuit Current (line-neutral fault at origin)

PEFC - Prospective Earth Fault Current (line-earth fault at circuit end)

PFC - The higher of PSCC or PEFC

Breaking Capacity

Standard MCB ratings (BS EN 60898):

6kA

Domestic

10kA

Commercial

25kA

Industrial

50kA

Heavy Industrial

Typical Ze Values
TN-C-S (PME):≤0.35Ω
TN-S:≤0.80Ω
TT:≤21Ω
Supply Details
Enter the external earth fault loop impedance
Ω

Measured at the origin of installation

Circuit Details (Optional)
Add R1+R2 to calculate earth fault current at circuit end
Ω

Leave blank for PSCC only

Data: BS 7671:2018+A2:2022 — Regulation 612.11, BS EN 60909

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

Prospective fault current is the maximum current that would flow under a short-circuit or earth fault condition. Every protective device must be capable of safely interrupting this current.

The calculation is straightforward: fault current equals the supply voltage divided by the total fault loop impedance. You must measure both line-to-neutral (PSCC) and line-to-earth (PEFC), then record the higher value. This figure is compared against the breaking capacity (Icn) of every protective device in the installation.

PFC = U\u2080 / Zs
U₀
= Nominal supply voltage (230V for single phase UK)
Zs
= Total fault loop impedance in ohms

BS 7671 Regulation 434.5.1

At the origin of a typical UK domestic installation, PFC commonly ranges from 1kA to 6kA. Installations close to a distribution transformer or on PME supplies may see significantly higher values, occasionally exceeding 16kA.

Quick Reference — Typical PFC by Loop Impedance

Prospective fault current at 230V for common Ze values

Regulation 434.5.1
Ze (Ω)PFC (A)PFC (kA)
0.123002.3
0.211501.15
0.356570.66
0.54600.46
0.82880.29

Values assume 230V supply and no additional internal impedance. Actual PFC at the origin will include meter tail impedance.

Practical Notes

Consumer Unit Conditional Ratings

Consumer units manufactured to BS EN 61439-3 are typically conditionally rated at 16kA. This rating is only valid when a 100A BS 88-3 HRC fuse is fitted upstream by the DNO. Without that fuse (e.g. on a direct MCCB feed), the board’s inherent breaking capacity — often just 6kA or 10kA — applies. Always confirm the upstream protection arrangement.

Cable Length Reduces Fault Current

Longer meter tails add impedance that reduces PFC at the consumer unit. Extending tails from 3m to 10m can drop PFC by 1-2kA. While this can help borderline installations, it should never be relied upon as a design strategy — it also affects disconnection times for protective devices.

PME Conversions and Legacy Boards

When an older TN-S installation is converted to PME (TN-C-S) by the DNO, the external impedance Ze often drops significantly — from 0.8 ohms down to 0.35 ohms or less. This can more than double the prospective fault current. Legacy consumer units with 3kA or 6kA breakers may become inadequate. Always re-verify PFC after any supply alteration.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch