Skip to content

Adiabatic Equation Calculator

Calculate minimum CPC and earthing conductor size using S = \u221A(I\u00B2t) / k per BS 7671

Reference Info & Formulas
What This Calculates
  • Minimum conductor size from adiabatic equation
  • Comparison with Table 54.7 simplified method
  • Correct k value for your conductor arrangement
  • Energy let-through (I\u00B2t)
Key References

Reg 543.1.3: Adiabatic equation

Table 54.2: k values (cables)

Table 54.3: k values (bare CPC)

Table 54.5: k values (separate CPC)

Table 54.6: k values (bonding)

Table 54.7: Simplified CPC sizing

Fault Parameters
Fault current and disconnection time for the circuit
A

Prospective earth fault current (PEFC)

s

0.4s for 32A circuits, 5s for distribution

Conductor Details
Material, insulation, and application of the protective conductor

Determines which BS 7671 table is used for k

For comparison with Table 54.7 simplified method

Data: BS 7671:2018+A2:2022 \u2014 Regulation 543.1.3, Tables 54.2\u201354.6

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How the Adiabatic Equation Works

The adiabatic equation determines whether a protective conductor can withstand the thermal energy released during a fault, before the protective device disconnects the supply.

During an earth fault, current flows through the protective conductor for the duration of the disconnection time. This current heats the conductor. The adiabatic equation checks that the conductor cross-section is large enough to absorb this energy without exceeding the insulation temperature limit.

S = √(I²t) / k
S
= Minimum conductor cross-sectional area (mm²)
I
= Fault current in amperes (RMS)
t
= Disconnection time of the protective device (seconds)
k
= Factor for conductor material and insulation type

BS 7671 Regulation 543.1.3

The term I\u00B2t represents the energy let-through of the fault in A\u00B2s. The k value encapsulates the thermal properties of the conductor and its insulation. A higher k value means the conductor can tolerate more energy per mm\u00B2 of cross-section.

Adiabatic Equation vs Table Method

BS 7671 offers two approaches for sizing protective conductors. The table method (Table 54.7) provides a quick lookup based on the line conductor size. The adiabatic equation (Regulation 543.1.3) provides a precise calculation based on actual fault conditions. In practice, the larger of the two results should be used.

When to Use Each Method

Use the table method for standard domestic circuits where T&E cable provides a fixed CPC size. Use the adiabatic equation when running a separate CPC, when fault currents are unusually high, or when verifying that a standard T&E CPC is adequate for the actual fault level at the installation.

k Values from BS 7671

Common k values for copper protective conductors

BS 7671 Tables 54.2\u201354.6
ApplicationInsulationk ValueBS 7671 Table
CPC within multi-core cablePVC 70°C115Table 54.2 / 54.4
CPC within multi-core cableXLPE 90°C143Table 54.2
Separate CPC, not bunchedPVC 70°C143Table 54.5
Separate CPC, not bunchedXLPE 90°C176Table 54.5
Bare CPC touching cable sheathAny159Table 54.3
Bonding conductorPVC 70°C115Table 54.6

Aluminium conductors have lower k values. For the full range, refer to BS 7671 directly.

Practical Examples

Example: 32A Ring Final

For a 32A ring final with PEFC of 800A, disconnection time 0.4s, copper CPC in PVC T&E cable (k = 115): S = \u221A(800\u00B2 \u00D7 0.4) / 115 = \u221A(256000) / 115 = 506.0 / 115 = 4.40mm\u00B2. The standard T&E CPC is 1.5mm\u00B2, which is adequate at this fault level because actual MCB trip times at 800A are well under 0.4s.

When Standard CPC Is Not Enough

If a circuit close to the consumer unit has a very high PEFC (e.g. 3000A) and the disconnection time is 5 seconds (distribution circuit), the adiabatic equation may require a CPC much larger than the standard T&E core. In such cases, a separate CPC or larger cable must be used.

BS 7671 Regulation References

Key regulations for protective conductor sizing

BS 7671:2018+A2:2022 Chapter 54
RegulationDescription
543.1.1General requirements for protective conductors
543.1.3Adiabatic equation for CPC sizing
543.1.4Simplified method using Table 54.7
Table 54.2k values for CPC incorporated in cables
Table 54.3k values for bare protective conductors
Table 54.4k values for CPC as a core in cable or bunched
Table 54.5k values for separate protective conductors not bunched
Table 54.6k values for bonding conductors
Table 54.7Minimum CPC sizes from line conductor cross-section

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch