Max Zs for 32A BS 88 Fuse
BS 7671 Table 41.4 — BS 7671:2018+A2:2022
Max Zs (0.4s)
1.04Ω
Testing Limit
0.83Ω
Max Zs (5s)
2.1Ω
Ia (0.4s)
210A
At a Glance
- Device
- BS 88 Fuse — 32A
- Standard
- BS 88
- Max Zs (0.4s)
- 1.04Ω
- Max Zs (5s)
- 2.1Ω
- Testing Limit (80%)
- 0.83Ω
- Ia (0.4s)
- 210A
About BS 88 Fuse
BS 88 fuses (also called HRC or HBC fuses) are high breaking capacity industrial fuses. They protect distribution board sub-circuits and main incomers. Their time/current characteristics differ from MCBs — disconnection time depends on the precise fault current level, not a fixed multiplier.
Typical Circuits for 32A BS 88 Fuse
| Circuit | Cable Size | Notes |
|---|---|---|
| Socket distribution | 6.0mm² | Industrial socket circuit |
Worked Example: Maximum Cable Run for 32A BS 88 Fuse
- Maximum Zs (tabulated) = 1.04Ω (BS 7671 Table 41.4)
- Testing limit (80%) = 1.04 × 0.8 = 0.83Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 0.83 − 0.35 = 0.48Ω
- Using 6mm² T&E: R1+R2 = 6.16 mΩ/m
- Maximum cable run = 0.48 ÷ 0.0061600000000000005 = 77.9m
On a TN-C-S (PME) supply with 6mm² cable, the maximum one-way cable run is approximately 77.9m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection Times
Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 32A: max Zs = 1.04Ω (0.4s) vs 2.1Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 1.04Ω | 0.83Ω |
| 5 seconds | 2.1Ω | 1.68Ω |
32A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 1.37Ω | 1.1Ω |
| MCB Type C | 0.68Ω | 0.54Ω |
| MCB Type D | 0.34Ω | 0.27Ω |
| BS 88 Fuse | 1.04Ω | 0.83Ω |