Max Zs for 25A BS 88 Fuse
BS 7671 Table 41.4 — BS 7671:2018+A2:2022
Max Zs (0.4s)
1.61Ω
Testing Limit
1.29Ω
Max Zs (5s)
3.2Ω
Ia (0.4s)
136A
At a Glance
- Device
- BS 88 Fuse — 25A
- Standard
- BS 88
- Max Zs (0.4s)
- 1.61Ω
- Max Zs (5s)
- 3.2Ω
- Testing Limit (80%)
- 1.29Ω
- Ia (0.4s)
- 136A
About BS 88 Fuse
BS 88 fuses (also called HRC or HBC fuses) are high breaking capacity industrial fuses. They protect distribution board sub-circuits and main incomers. Their time/current characteristics differ from MCBs — disconnection time depends on the precise fault current level, not a fixed multiplier.
Worked Example: Maximum Cable Run for 25A BS 88 Fuse
- Maximum Zs (tabulated) = 1.61Ω (BS 7671 Table 41.4)
- Testing limit (80%) = 1.61 × 0.8 = 1.29Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 1.29 − 0.35 = 0.94Ω
- Using 4mm² T&E: R1+R2 = 9.22 mΩ/m
- Maximum cable run = 0.94 ÷ 0.00922 = 102m
On a TN-C-S (PME) supply with 4mm² cable, the maximum one-way cable run is approximately 102m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection Times
Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 25A: max Zs = 1.61Ω (0.4s) vs 3.2Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 1.61Ω | 1.29Ω |
| 5 seconds | 3.2Ω | 2.56Ω |
25A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 1.75Ω | 1.4Ω |
| MCB Type C | 0.87Ω | 0.7Ω |
| MCB Type D | 0.44Ω | 0.35Ω |
| BS 88 Fuse | 1.61Ω | 1.29Ω |