Max Zs Tables

Maximum earth fault loop impedance values for protective devices

BS 7671:2018+A2:2022 Tables 41.2, 41.3, 41.4

0.4s Disconnection

Final circuits (sockets, lighting)

5s Disconnection

Distribution circuits

80% Rule

Testing limit shown in blue

Quick Lookup

MCB Type B (BS EN 60898)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
67.285.827.285.82
104.373.504.373.50
162.732.182.732.18
202.191.752.191.75
251.751.401.751.40
321.371.101.371.10
401.090.871.090.87
500.870.700.870.70
630.690.550.690.55
800.550.440.550.44
1000.440.350.440.35
1250.350.280.350.28
MCB Type C (BS EN 60898)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
63.642.913.642.91
102.191.752.191.75
161.371.101.371.10
201.090.871.090.87
250.870.700.870.70
320.680.540.680.54
400.550.440.550.44
500.440.350.440.35
630.350.280.350.28
800.270.220.270.22
1000.220.180.220.18
1250.170.140.170.14
MCB Type D (BS EN 60898)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
61.821.461.821.46
101.090.871.090.87
160.680.540.680.54
200.550.440.550.44
250.440.350.440.35
320.340.270.340.27
400.270.220.270.22
500.220.180.220.18
630.170.140.170.14
800.140.110.140.11
1000.110.090.110.09
1250.090.070.090.07
BS 88 Fuses (gG)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
68.096.4712.8410.27
104.853.887.045.63
162.572.063.973.18
201.671.342.772.22
251.371.102.191.75
320.990.791.751.40
400.770.621.281.02
500.570.460.990.79
630.430.340.770.62
800.290.230.550.44
1000.210.170.390.31
1250.170.140.310.25
BS 1361 Fuses
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
59.927.9415.5712.46
153.122.504.753.80
201.621.302.662.13
301.090.871.751.40
450.550.440.900.72
BS 3036 Semi-enclosed Fuses
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
59.587.6618.4014.72
152.762.215.224.18
202.141.714.143.31
301.261.012.642.11
450.830.661.661.33

Important Notes

  • 80% Rule: When testing, measured Zs should be ≤80% of tabulated value to account for conductor resistance at operating temperature.
  • 0.4s: Required for socket outlets and circuits supplying portable equipment (Reg. 411.3.2.2).
  • 5s: Permitted for distribution circuits and fixed equipment in certain conditions (Reg. 411.3.2.3).
  • • Values assume Cmin = 0.95 and nominal voltage U₀ = 230V.
  • • For TT systems, RCD protection is typically required regardless of Zs values.