Max Zs Tables

Maximum earth fault loop impedance values for protective devices

BS 7671:2018+A2:2022 Tables 41.2, 41.3, 41.4

0.4s Disconnection

Final circuits (sockets, lighting)

5s Disconnection

Distribution circuits

80% Rule

Testing limit shown in blue

MCB Type B (BS EN 60898)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
67.285.827.285.82
104.373.504.373.50
162.732.182.732.18
202.191.752.191.75
251.751.401.751.40
321.371.101.371.10
401.090.871.090.87
500.870.700.870.70
630.690.550.690.55
800.550.440.550.44
1000.440.350.440.35
1250.350.280.350.28
MCB Type C (BS EN 60898)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
63.642.917.285.82
102.191.754.373.50
161.371.102.732.18
201.090.872.191.75
250.870.701.751.40
320.680.541.371.10
400.550.441.090.87
500.440.350.870.70
630.350.280.690.55
800.270.220.550.44
1000.220.180.440.35
1250.170.140.350.28
MCB Type D (BS EN 60898)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
61.821.463.642.91
101.090.872.191.75
160.680.541.371.10
200.550.441.090.87
250.440.350.870.70
320.340.270.680.54
400.270.220.550.44
500.220.180.440.35
630.170.140.350.28
800.140.110.270.22
1000.110.090.220.18
1250.090.070.170.14
BS 88 Fuses (gG)
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
162.421.944.803.84
201.841.473.702.96
251.611.293.202.56
321.040.832.101.68
400.870.701.701.36
500.680.541.401.12
630.540.431.100.88
800.420.340.840.67
1000.340.270.670.54
1250.270.220.540.43
1600.210.170.420.34
2000.170.140.340.27
BS 1361 Fuses
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
510.908.7221.8017.44
153.122.506.204.96
202.421.944.803.84
301.611.293.202.56
451.040.832.101.68
BS 3036 Semi-enclosed Fuses
Rating (A)
0.4s
Max Zs (Ω)
0.4s Test
80% (Ω)
5s
Max Zs (Ω)
5s Test
80% (Ω)
59.587.6618.4014.72
152.762.215.224.18
202.141.714.143.31
301.261.012.642.11
450.830.661.661.33

Important Notes

  • 80% Rule: When testing, measured Zs should be ≤80% of tabulated value to account for conductor resistance at operating temperature.
  • 0.4s: Required for socket outlets and circuits supplying portable equipment (Reg. 411.3.2.2).
  • 5s: Permitted for distribution circuits and fixed equipment in certain conditions (Reg. 411.3.2.3).
  • • Values assume Cmin = 0.95 and nominal voltage U₀ = 230V.
  • • For TT systems, RCD protection is typically required regardless of Zs values.