Skip to content

Voltage Drop Calculator

Check voltage drop against BS 7671 limits for any cable installation

Reference Info & Formulas
BS 7671 Limits
Lighting circuits:3%
Other circuits:5%

Regulation 525.1 allows up to 5% total from origin. For private supplies from public LV, 3% is allowed for lighting.

Formula

Vd = (mV/A/m × Ib × L) / 1000

Where mV/A/m values are from BS 7671 Tables 4D1B etc.

Circuit Details
Enter the load and cable information
A
m

Data: BS 7671:2018+A2:2022 — Tables 4D1B–4J1B, Regulation 525

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

Voltage drop is calculated from the cable's millivolt-per-amp-per-metre value, the design current, and the cable run length.

Every cable has resistance, and current flowing through that resistance creates a voltage drop along the length of the conductor. BS 7671 limits this drop to ensure equipment receives adequate voltage at the furthest point of the circuit.

Vd = (mV/A/m × Ib × L) / 1000
mV/A/m
= Millivolt drop per amp per metre (from Table 4D5)
Ib
= Design current of the circuit in amps
L
= Cable run length in metres (one way)

BS 7671 Appendix 4, Regulation 525.1

The maximum permitted drop is 3% for lighting (6.9V at 230V) and 5% for all other circuits (11.5V at 230V). For cables larger than 16mm², the reactive component of impedance becomes significant and the calculation should account for both resistance and reactance.

Quick Reference — mV/A/m Values (T&E, Method C)

Millivolt drop per amp per metre for twin and earth cables

Table 4D5
Cable Size (mm²)mV/A/mMax Length at 32A / 5% (m)
1.52912
2.51820
41133
67.349
104.482
162.8128

Max length calculated as (11500) / (mV/A/m × 32), rounded down. Actual lengths depend on design current.

Practical Notes

Design for 3-4%, Not 5%

Although BS 7671 allows 5% for power circuits, designing for 3-4% leaves margin for supply voltage fluctuations. UK supply can legally vary between 216.2V and 253V (230V -6% / +10%). A circuit already at 5% drop on a low-supply day could cause equipment issues.

Power Loss Is Quadratic

For resistive loads such as showers and heaters, power output drops with the square of voltage (P = V²/R). A 10V drop on a 10.5kW shower reduces output by approximately 8% — noticeably weaker water heating at higher flow rates.

Cumulative Drop Matters

Voltage drop limits apply from the origin of the installation to the final load. If sub-mains consume 2% of the budget, only 3% remains for the final circuit (at the 5% total limit). Always account for the full cable route from meter to load.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch