Skip to content

Shower Cable Size Calculator

Calculate cable size, MCB rating, and voltage drop for electric shower circuits

Reference Info & Formulas
Quick Reference

≤ 8.5 kW: 6mm² usually ok

9.5 kW: 10mm² recommended

≥ 10.5 kW: 10mm² minimum

Always check installation method and run length

Requirements

Dedicated radial circuit

30mA RCD (Type A)

DP isolation switch

Part P notifiable

Shower Details
Select the shower power rating
Cable Route
Enter cable run details

Data: BS 7671:2018+A2:2022 — Table 4D5, Section 701

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How This Calculator Works

Shower circuits carry a continuous load with no diversity applied — the cable must handle 100% of the rated power.

The design current is calculated as Ib = P / V. For example, a 10.5kW shower at 230V draws 10500 / 230 = 45.7A. No diversity reduction is permitted because showers draw their full rated current whenever running.

Ib = P / V
P
= Shower power rating in watts
V
= Nominal supply voltage (230V)

BS 7671 Appendix 4

The cable is selected from Table 4D5 such that the tabulated rating (after correction factors for ambient temperature, grouping, and thermal insulation) exceeds the MCB rating. The MCB is typically 40A for showers up to 9kW, or 45A for 9.5kW and above.

Quick Reference — Shower Cable Sizing

Common shower ratings and cable requirements (Method C)

Table 4D5
Shower (kW)Design Current (A)Cable SizeMCB Rating
7.231.36mm²32A
8.537.06mm²40A
9.541.310mm²45A
10.545.710mm²45A

Based on Method C (clipped direct), 30°C ambient, no thermal insulation contact.

Practical Notes

Thermal Insulation Halves Capacity

Under Method 101 (cable enclosed in insulation for over 0.5m), a 10mm² cable drops from 64A to roughly 32A. For a 10.5kW shower in an insulated loft space, this is insufficient — 16mm² T&E is required to maintain adequate capacity.

Type A RCD for Electronic Showers

Amendment 3 (2022) mandates a Type A RCD for circuits supplying equipment with electronic controls. Most modern showers use electronic temperature regulation, making a Type A (or Type F) RCBO the correct choice for new installations.

Dedicated Circuit Required

Every electric shower must have its own dedicated radial circuit from the consumer unit. Sharing a circuit causes voltage dip when the shower operates, leading to flickering lights and reduced performance on other connected loads.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch