Shower Cable Size Calculator
Calculate cable size, MCB rating, and voltage drop for electric shower circuits
Reference Info & Formulas
≤ 8.5 kW: 6mm² usually ok
9.5 kW: 10mm² recommended
≥ 10.5 kW: 10mm² minimum
Always check installation method and run length
Dedicated radial circuit
30mA RCD (Type A)
DP isolation switch
Part P notifiable
Data: BS 7671:2018+A2:2022 — Table 4D5, Section 701
For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.
How This Calculator Works
Shower circuits carry a continuous load with no diversity applied — the cable must handle 100% of the rated power.
The design current is calculated as Ib = P / V. For example, a 10.5kW shower at 230V draws 10500 / 230 = 45.7A. No diversity reduction is permitted because showers draw their full rated current whenever running.
Ib = P / V- P
- = Shower power rating in watts
- V
- = Nominal supply voltage (230V)
BS 7671 Appendix 4
The cable is selected from Table 4D5 such that the tabulated rating (after correction factors for ambient temperature, grouping, and thermal insulation) exceeds the MCB rating. The MCB is typically 40A for showers up to 9kW, or 45A for 9.5kW and above.
Quick Reference — Shower Cable Sizing
Common shower ratings and cable requirements (Method C)
Table 4D5| Shower (kW) | Design Current (A) | Cable Size | MCB Rating |
|---|---|---|---|
| 7.2 | 31.3 | 6mm² | 32A |
| 8.5 | 37.0 | 6mm² | 40A |
| 9.5 | 41.3 | 10mm² | 45A |
| 10.5 | 45.7 | 10mm² | 45A |
Based on Method C (clipped direct), 30°C ambient, no thermal insulation contact.
Practical Notes
Thermal Insulation Halves Capacity
Type A RCD for Electronic Showers
Dedicated Circuit Required
Frequently Asked Questions
SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.