Skip to content

Garden Office & Outbuilding Supply Calculator

Size the SWA supply cable for a garden office, workshop, or outbuilding with automatic load estimation and diversity

Reference Info & Formulas
Quick Reference

Garden office (basic): 4mm² SWA

Workshop / gym: 6-10mm² SWA

Annexe with shower: 10-16mm² SWA

Always use SWA for underground runs

Key Requirements

SWA cable buried at 500mm min

Cable tiles and warning tape

30mA RCD at sub-board

Earth rod if PME supply

Part P notifiable work

SWA Ratings (Buried)

4mm²: 40A

6mm²: 51A

10mm²: 69A

16mm²: 91A

25mm²: 116A

Table 4D4A, Method D, 30°C

Outbuilding Details
Select the type of outbuilding and supply
Appliance Checklist
Tick the appliances for your outbuilding to estimate the load
Cable Route
Enter the cable run distance and ground conditions

Distance from main CU to outbuilding

Minimum 0.5m recommended

Data: BS 7671:2018+A2:2022 — Table 4D4A, IET On-Site Guide Tables 1A/1B

For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.

How Does the Outbuilding Supply Calculator Work?

This calculator sizes the SWA sub-main cable from your main consumer unit to the outbuilding, applying diversity to estimate realistic maximum demand.

Unlike a simple cable size calculator, this tool starts by estimating your total load from an appliance checklist. It then applies diversity factors per the IET On-Site Guide to calculate a realistic maximum demand \u2014 because not all appliances run simultaneously at full power. The diversified demand determines the design current, which drives the cable and protection sizing.

Ib = P_diversified / V
P_diversified
= Total diversified demand in watts
V
= Nominal supply voltage (230V single phase, 400V three phase)

BS 7671 Appendix 4

The cable is then selected from BS 7671 Table 4D4A for SWA cable buried direct (Method D). Ambient temperature correction is applied, and voltage drop is checked against the 5% limit (11.5V at 230V).

What Diversity Factors Are Applied?

Diversity allows you to reduce the total connected load to a more realistic figure, based on the probability that not all appliances operate at full power simultaneously. The IET On-Site Guide Tables 1A and 1B provide standard diversity allowances for domestic premises.

Diversity factors applied per IET On-Site Guide

IET On-Site Guide Tables 1A/1B
Load TypeDiversity RuleExample
Lighting66% of total connected500W → 330W
SocketsFirst 10A at 100% + 40% of remainder4kW → 2,980W
CookerFirst 10A at 100% + 30% remainder + 5A socket8kW → 5,810W
Shower100% (no diversity)8.5kW → 8,500W
EV Charger100% (no diversity)7.4kW → 7,400W
Heating100% largest + 40% remainder3kW + 2kW → 3,800W

Other dedicated loads (hot tub, A/C, power tools) are taken at 100% as conservative single-appliance allowances.

What SWA Cable Sizes Are Available?

SWA 2-core copper cable ratings \u2014 buried direct (Method D)

BS 7671 Table 4D4A Column 7
Cable SizeCurrent Rating (A)mV/A/mTypical Use
4mm²409.5Small shed, basic garden office
6mm²516.4Garden office with heater
10mm²693.8Workshop or studio
16mm²912.4Annexe with shower/cooker
25mm²1161.55Full annexe/dwelling

Ratings at 30\u00B0C ambient. Apply correction factors for grouping and higher ambient temperatures.

Why Is PME Earthing a Concern for Outbuildings?

Most UK domestic properties use a PME (TN-C-S) earthing arrangement where the neutral and earth are combined in the supply cable (PEN conductor). If this PEN conductor is lost or damaged, the entire protective earth rises to a dangerous potential. For equipment inside the main building this risk is managed, but for a separate outbuilding connected by a long cable run, the consequences can be severe.

PME Earth Rod Requirement

Regulation 411.4.2 restricts the use of PME earthing for the exposed-conductive-parts of equipment in an outbuilding. An earth electrode (earth rod) must be installed at the outbuilding and connected to the sub-board MET. The SWA armour provides the CPC back to the main installation, but the outbuilding must have its own local earth reference.

TN-S Supply

If your property has a TN-S supply (separate earth conductor from the DNO), you can extend the main earth to the outbuilding via the SWA armour without needing an additional earth rod. Check your supply type at the main intake position.

Installation Best Practice for Buried SWA

Cable Route Protection

Buried SWA cable must be installed at a minimum depth of 500mm in gardens (600mm under driveways). The cable should be laid on a 50mm bed of sand, covered with a further 50mm of sand, then protected with cable tiles or covers. Warning tape must be placed 150mm above the cable to alert anyone digging in the future.

Cable Gland Selection

SWA cable requires proper gland termination at both ends to maintain IP rating, mechanical integrity, and earth continuity via the armour. Use the SparkyHub SWA Cable Gland Calculator to select the correct CW or BW gland for your cable size.

Part P and DNO Notification

A new sub-main to an outbuilding is Part P notifiable work. If the total load is high or the existing supply fuse is close to capacity, you may also need to notify the DNO. Consider requesting a supply upgrade if the existing 60A or 80A supply cannot accommodate the additional demand.

Frequently Asked Questions

SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.

Related Calculators

Built by Taro Schenker · Need a website for your trade business? Get in touch