Hot Tub Cable Size Calculator
Calculate cable size, MCB rating, and RCD requirements for hot tub installations
Reference Info & Formulas
2.5 kW (13A plug): No hardwired circuit needed
4.5 kW (20A): 4mm² SWA usually ok
7.5 kW (32A): 6mm² SWA typical
SWA required for outdoor/underground runs
Dedicated radial circuit
30mA Type A RCD
DP isolator within sight
IP65+ outdoor enclosure
Part P notifiable
Data: BS 7671:2018+A2:2022 — Tables 4D4A, 4D5, Section 701
For guidance only. The responsibility for any electrical installation lies with the qualified person carrying out the work. Always verify calculations independently and apply professional judgement.
How Does This Hot Tub Cable Size Calculator Work?
Hot tub circuits are dedicated radial circuits supplying a continuous resistive and motor load — cable must handle 100% of the rated power with no diversity.
The design current is calculated as Ib = P / V. For example, a 7.5kW hot tub at 230V draws 7500 / 230 = 32.6A. No diversity is applied because the heater and pump operate simultaneously at full rated power during the heating cycle.
Ib = P / V- P
- = Hot tub power rating in watts
- V
- = Nominal supply voltage (230V)
BS 7671 Appendix 4
Correction factors are then applied to derate the cable's tabulated current capacity: ambient temperature (Ca from Table 4B1), grouping (Cg from Table 4C1), and thermal insulation (Ci from Table 52.2). The cable is selected so that its derated capacity exceeds the MCB rating, which must in turn exceed the design current: Ib ≤ In ≤ Iz.
What Cable Sizes Do Hot Tubs Require?
SWA cable sizing for common hot tub ratings (buried direct, Method D)
Table 4D4A| Hot Tub (kW) | Design Current (A) | Cable Size | MCB Rating |
|---|---|---|---|
| 2.5 | 10.9 | 2.5mm² | 16A |
| 4.5 | 19.6 | 2.5mm² | 20A |
| 7.5 | 32.6 | 6mm² | 32A |
| 9 | 39.1 | 6mm² | 40A |
| 11 | 47.8 | 10mm² | 50A |
Based on Method D (buried direct), 30\u00B0C ambient, no grouping. Always verify voltage drop for your cable length.
Why Is SWA Cable Required for Outdoor Hot Tubs?
SWA cable provides essential mechanical protection for outdoor and underground installations. The steel wire armour protects the conductors from damage during installation and from external impacts such as garden tools, and it also serves as the circuit protective conductor (CPC). T&E cable lacks this protection and must not be used for buried or exposed outdoor runs.
PME Earthing Restriction
SWA Gland Selection
Practical Installation Notes for Hot Tub Circuits
Local Isolation Required
Voltage Drop on Long Runs
Part P Notification
Frequently Asked Questions
SparkyHub is a free resource built by Taro Schenker — I build websites for trade businesses too.