Max Zs for 25A Type B MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

1.75Ω

Testing Limit

1.4Ω

Max Zs (5s)

1.75Ω

Ia (0.4s)

125A

At a Glance

Device
MCB Type B25A
Standard
BS EN 60898
Max Zs (0.4s)
1.75Ω
Max Zs (5s)
1.75Ω
Testing Limit (80%)
1.4Ω
Ia (0.4s)
125A

About MCB Type B

Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.

Typical Circuits for 25A Type B MCB

Recommended cable sizes for 25A Type B MCB circuits
CircuitCable SizeNotes
Storage heater2.5–4.0mm² T&EDedicated supply
Radial circuit (workshop)4.0mm² T&EHigher demand areas

Worked Example: Maximum Cable Run for 25A MCB Type B

  1. Maximum Zs (tabulated) = 1.75Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 1.75 × 0.8 = 1.4Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 1.4 − 0.35 = 1.05Ω
  5. Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
  6. Maximum cable run = 1.05 ÷ 0.01482 = 70.9m

On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 70.9m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s and 5s Disconnection — Same Values for Type B

For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 1.75Ω for both disconnection times at 25A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).

25A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B1.75Ω1.4Ω
MCB Type C0.87Ω0.7Ω
MCB Type D0.44Ω0.35Ω
BS 88 Fuse1.61Ω1.29Ω

Frequently Asked Questions