Skip to content

Max Zs for 25A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.87Ω

Testing Limit

0.7Ω

Max Zs (5s)

1.75Ω

Ia (0.4s)

250A

At a Glance

Device
MCB Type C25A
Standard
BS EN 60898
Max Zs (0.4s)
0.87Ω
Max Zs (5s)
1.75Ω
Testing Limit (80%)
0.7Ω
Ia (0.4s)
250A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 25A Type C MCB

Recommended cable sizes for 25A Type C MCB circuits
CircuitCable SizeNotes
Commercial HVAC4.0mm²Larger air handling units

Worked Example: Maximum Cable Run for 25A MCB Type C

  1. Maximum Zs (tabulated) = 0.87Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.87 × 0.8 = 0.7Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 0.7 − 0.35 = 0.35Ω
  5. Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
  6. Maximum cable run = 0.35 ÷ 0.01482 = 23.6m

On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 23.6m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Different Values for Type C

Type C MCBs require 10× In for 0.4s disconnection but only 5× In for 5s. At 25A: max Zs = 0.87Ω (0.4s) vs 1.75Ω (5s). For distribution circuits (5s allowed), you have nearly double the impedance budget. Final circuits serving socket outlets must still meet the 0.4s limit.

Disconnection TimeMax ZsTesting Limit (80%)
0.4 seconds0.87Ω0.7Ω
5 seconds1.75Ω1.4Ω

25A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B1.75Ω1.4Ω
MCB Type C0.87Ω0.7Ω
MCB Type D0.44Ω0.35Ω
BS 88 Fuse1.61Ω1.29Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch