Max Zs for 20A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

1.09Ω

Testing Limit

0.87Ω

Max Zs (5s)

1.09Ω

Ia (0.4s)

200A

At a Glance

Device
MCB Type C20A
Standard
BS EN 60898
Max Zs (0.4s)
1.09Ω
Max Zs (5s)
1.09Ω
Testing Limit (80%)
0.87Ω
Ia (0.4s)
200A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 20A Type C MCB

Recommended cable sizes for 20A Type C MCB circuits
CircuitCable SizeNotes
Motor circuit (medium)2.5–4.0mm²Pump motors, compressors

Worked Example: Maximum Cable Run for 20A MCB Type C

  1. Maximum Zs (tabulated) = 1.09Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 1.09 × 0.8 = 0.87Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 0.87 − 0.35 = 0.52Ω
  5. Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
  6. Maximum cable run = 0.52 ÷ 0.01482 = 35.1m

On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 35.1m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Different Values for Type C

At 20A, the max Zs values are the same for both disconnection times: 1.09Ω.

20A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B2.19Ω1.75Ω
MCB Type C1.09Ω0.87Ω
MCB Type D0.55Ω0.44Ω
BS 88 Fuse1.67Ω1.34Ω
BS 1361 Fuse1.62Ω1.3Ω
BS 3036 Semi-enclosed Fuse2.14Ω1.71Ω