Skip to content

Max Zs for 16A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

1.37Ω

Testing Limit

1.1Ω

Max Zs (5s)

1.37Ω

Ia (0.4s)

160A

At a Glance

Device
MCB Type C16A
Standard
BS EN 60898
Max Zs (0.4s)
1.37Ω
Max Zs (5s)
1.37Ω
Testing Limit (80%)
1.1Ω
Ia (0.4s)
160A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 16A Type C MCB

Recommended cable sizes for 16A Type C MCB circuits
CircuitCable SizeNotes
Air conditioning unit2.5mm²Split system with compressor start current

Worked Example: Maximum Cable Run for 16A MCB Type C

  1. Maximum Zs (tabulated) = 1.37Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 1.37 × 0.8 = 1.1Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 1.1 − 0.35 = 0.75Ω
  5. Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
  6. Maximum cable run = 0.75 ÷ 0.01482 = 50.6m

On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 50.6m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Different Values for Type C

At 16A, the max Zs values are the same for both disconnection times: 1.37Ω.

16A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B2.73Ω2.18Ω
MCB Type C1.37Ω1.1Ω
MCB Type D0.68Ω0.54Ω
BS 88 Fuse2.57Ω2.06Ω

Frequently Asked Questions