Max Zs for 16A Type D MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
0.68Ω
Testing Limit
0.54Ω
Max Zs (5s)
0.68Ω
Ia (0.4s)
320A
At a Glance
- Device
- MCB Type D — 16A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 0.68Ω
- Max Zs (5s)
- 0.68Ω
- Testing Limit (80%)
- 0.54Ω
- Ia (0.4s)
- 320A
About MCB Type D
Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.
Typical Circuits for 16A Type D MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Transformer primary | 2.5mm² | Control transformer with magnetising inrush |
Worked Example: Maximum Cable Run for 16A MCB Type D
- Maximum Zs (tabulated) = 0.68Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 0.68 × 0.8 = 0.54Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 0.54 − 0.35 = 0.19Ω
- Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
- Maximum cable run = 0.19 ÷ 0.01482 = 12.8m
On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 12.8m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection — Significant Difference for Type D
At 16A, the max Zs values for Type D are 0.68Ω for both disconnection times.
16A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 2.73Ω | 2.18Ω |
| MCB Type C | 1.37Ω | 1.1Ω |
| MCB Type D | 0.68Ω | 0.54Ω |
| BS 88 Fuse | 2.57Ω | 2.06Ω |