Max Zs for 20A Type D MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.55Ω

Testing Limit

0.44Ω

Max Zs (5s)

0.55Ω

Ia (0.4s)

400A

At a Glance

Device
MCB Type D20A
Standard
BS EN 60898
Max Zs (0.4s)
0.55Ω
Max Zs (5s)
0.55Ω
Testing Limit (80%)
0.44Ω
Ia (0.4s)
400A

About MCB Type D

Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.

Typical Circuits for 20A Type D MCB

Recommended cable sizes for 20A Type D MCB circuits
CircuitCable SizeNotes
Welding transformer4.0mm²Resistance welding equipment

Worked Example: Maximum Cable Run for 20A MCB Type D

  1. Maximum Zs (tabulated) = 0.55Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.55 × 0.8 = 0.44Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 0.44 − 0.35 = 0.09Ω
  5. Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
  6. Maximum cable run = 0.09 ÷ 0.01482 = 6.1m

On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 6.1m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Significant Difference for Type D

At 20A, the max Zs values for Type D are 0.55Ω for both disconnection times.

20A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B2.19Ω1.75Ω
MCB Type C1.09Ω0.87Ω
MCB Type D0.55Ω0.44Ω
BS 88 Fuse1.67Ω1.34Ω
BS 1361 Fuse1.62Ω1.3Ω
BS 3036 Semi-enclosed Fuse2.14Ω1.71Ω