Skip to content

Earth Fault Loop Impedance Guide

Zs & Ze testing, max values, 80% rule, earthing systems, and remedial strategies

BS 7671 Reg 411.3–411.4, Tables 41.2–41.5 & IET Guidance Note 3

What is Earth Fault Loop Impedance?

Earth fault loop impedance (Zs) is the total impedance of the fault current path from the point of a fault, through the circuit protective conductor (CPC), back to the supply transformer. It determines how much fault current flows — and therefore how quickly the protective device disconnects. The lower the Zs, the higher the fault current, and the faster the disconnection.

Zs = Ze + (R1 + R2)

Ze = external loop impedance (DNO supply) • R1 = line conductor resistance • R2 = CPC resistance

Earthing Systems & Loop Paths

TN-SSeparate neutral & earth

Loop path: Line → Fault → CPC → Cable sheath/armour → Transformer neutral

Typical max Ze: ≤ 0.8 Ω

Common in older urban areas. Lead sheath provides reliable low-impedance path.

TN-C-S (PME)Combined PEN conductor

Loop path: Line → Fault → CPC → PME link → Combined PEN → Transformer neutral

Typical max Ze: ≤ 0.35 Ω

Most common modern UK residential supply. Multiple earth points give very low Ze.

TTLocal earth electrode

Loop path: Line → Fault → CPC → Earth electrode → Mass of earth → Transformer earth

Typical max Ze: > 20 Ω (can be 100s Ω)

RCDs mandatory — overcurrent devices cannot achieve ADS. Common in rural areas.

Maximum Disconnection Times (Reg 411.3.2)

SystemCircuit TypeMax TimeRegulation
TNFinal circuit ≤ 32 A (with sockets)0.4 sReg 411.3.2.2
TNFinal circuit ≤ 32 A (fixed equipment)0.4 sReg 411.3.2.2
TNDistribution circuit5.0 sReg 411.3.2.3
TTFinal circuit ≤ 32 A0.2 sReg 411.3.2.4
TTDistribution circuit1.0 sReg 411.3.2.4

Maximum Zs Values — MCBs (Tables 41.3)

230 V systems, 0.4 s disconnection time. Values calculated from Zs = (0.95 × U₀) / Ia.

Rating (In)Type B (Ω)Type C (Ω)Type D (Ω)
6 A7.673.831.92
10 A4.602.301.15
16 A2.871.440.72
20 A2.301.150.57
32 A1.440.720.36
40 A1.150.460.29
50 A0.920.460.23
63 A0.730.360.18

Maximum Zs Values — Fuses (Tables 41.2 & 41.4)

RatingBS 88-2 gG (Ω)BS 1361 (Ω)BS 3036 (Ω)
5 A10.459.58
15 A3.285.35
20 A1.771.703.83
30/32 A1.041.152.64
45 A0.600.60

The 80% Rule (Temperature Correction)

BS 7671 table values assume conductors at maximum operating temperature (70 °C for PVC). On-site tests are done at ambient (~20 °C), so conductor resistance is lower than it would be under full load.

Copper resistance increases by approximately 20% from 20 °C to 70 °C. To account for this, multiply the table value by 0.8 — if your measured Zs is below this 80% figure, the circuit will remain compliant even at full operating temperature.

Test limit = Table Zs × 0.8

80% Values — Common MCB Ratings
RatingType B (100%)Type B (80%)Type C (100%)Type C (80%)
6 A7.676.133.833.07
10 A4.603.682.301.84
16 A2.872.301.441.15
20 A2.301.841.150.92
32 A1.441.150.720.58
40 A1.150.920.460.37

Ze Measurement Procedure

1

Isolate the Installation

Follow safe isolation procedure. Prove dead using a GS38 compliant voltage indicator.

2

Disconnect Main Earthing Conductor

Remove the main earthing conductor from the MET to prevent parallel paths through gas/water pipes.

3

Connect Tester

Connect loop impedance tester between incoming line and the disconnected earthing conductor.

4

Perform High-Current Test

Use a high-current test (typically 20–25 A) for maximum accuracy at the origin.

5

Compare Against DNO Declared Values

TN-C-S ≤ 0.35 Ω, TN-S ≤ 0.8 Ω. Record the result.

6

Reconnect Earthing Conductor

Immediately reconnect the main earthing conductor and main bonding conductors.

Zs Testing Methods

High-Current Test

Injects ~23 A into the fault loop. Gives the most accurate and repeatable results.

Limitation: Trips any RCD/RCBO on the circuit (exceeds 30 mA threshold). Must bypass or disconnect RCDs first.

Best used at the origin or on non-RCD-protected circuits.

No-Trip (Low Current) Test

Uses ~15 mA — stays below 30 mA RCD threshold. 3-wire version uses neutral as reference for noise filtering.

Limitation: Less accurate below 1.0 Ω. Can be affected by standing leakage from connected appliances.

Best used on RCD/RCBO-protected circuits where bypassing is impractical.

Calculation Method (Zs = Ze + R1+R2)

Often the preferred method for initial verification. Measure Ze at the origin, then measure R1+R2 at the furthest point of each circuit using a low-resistance ohmmeter during dead testing.

Zs = Ze + (R1 + R2)
  • - More stable and repeatable than live loop testing
  • - Preferred by NICEIC — removes “fruit machine” variability of low-current testers
  • - Useful for circuits at height (lighting) or where live testing is impractical
  • - R1+R2 values measured at ambient — apply 80% rule to the calculated Zs

RCD Protection — Max Zs (Table 41.5)

When a circuit is protected by an RCD, the max Zs depends on the RCD sensitivity, not the overcurrent device.

RCD Sensitivity (IΔn)Max Permitted Zs
30 mA1,667 Ω
100 mA500 Ω
300 mA167 Ω
500 mA100 Ω

Diagnosing & Fixing High Zs

CauseSymptomRemedy
Excessive circuit lengthZs rises with distance from DBIncrease CPC size or add parallel CPC
Undersized CPCHigh R1+R2 relative to cable lengthUpgrade CPC or use larger cable
Loose/corroded connectionsErratic readings, higher than expectedRe-terminate, clean, and tighten all joints
High Ze from DNOZe exceeds declared maximumReport to DNO; install RCD protection
Damaged CPCVery high or open-circuit readingLocate and repair/replace damaged section

EICR Classification for Zs Results

ConditionCode
Measured Zs exceeds 100% table value — ADS cannot be guaranteedC2
Measured Zs exceeds 80% limit but within 100% table valueC3
Ze exceeds DNO declared maximumC2
TT earth electrode Ra exceeds 200 Ω (seasonal instability risk)C3

Important Warnings

  • - Always reconnect earthing immediately after Ze testing — the installation is unprotected while disconnected
  • - High-current loop tests trip RCDs — bypass or disconnect before testing, and reconnect immediately after
  • - Never test Zs on a circuit that is dead — loop impedance testers require a live supply
  • - TT systems: Earth electrode resistance varies seasonally — test during dry conditions for worst-case values
  • - Three-phase: Test each phase individually (L1-E, L2-E, L3-E) and record all values

Key Points

  • - Zs = Ze + (R1+R2) — total impedance from fault point back to transformer
  • - Compare measured values against 80% of table values (temperature-adjusted limits)
  • - TN systems: overcurrent devices (MCBs/fuses) provide ADS within 0.4 s for final circuits
  • - TT systems: RCDs are mandatory — overcurrent devices alone cannot achieve ADS
  • - The calculation method (Ze + R1+R2) is often more reliable than live loop testing
  • - Record all values on the Schedule of Test Results — both Ze and Zs for each circuit

Built by Taro Schenker · Need a website for your trade business? Get in touch