Skip to content

Safe Isolation Procedure

Step-by-step guide to safely isolating electrical circuits

HSE GS38, Electricity at Work Regulations 1989, BS 7671

Safety Critical Procedure

Safe isolation must be carried out every time before working on or near electrical circuits. Approximately 30 fatal electrical accidents occur in UK workplaces each year, with ~1,000 non-fatal incidents reported (RIDDOR). As little as 50mA can cause ventricular fibrillation. The EAWR 1989 imposes absolute duties — they must be met regardless of cost or difficulty.

The 6 Steps

1Identify the Circuit

Identify the circuit(s) to be worked on using drawings, schedules, or labelling at the distribution board.

  • Check circuit charts/schedules at the DB
  • Confirm which circuits supply the work area
  • Consider all sources of supply (multiple DBs, sub-mains, UPS, generators, PV)
  • Never rely solely on labels — they may be inaccurate from unrecorded modifications
  • Where possible, verify by checking the intended load turns off when the breaker operates
2Switch Off

Switch off the supply using the appropriate isolator, MCB, or main switch.

  • Use the correct isolating device for the circuit
  • Ensure it provides full disconnection (all poles)
  • For TT systems, both line and neutral may need isolation
  • Never rely on an MCB alone if a separate isolator exists
3Secure the Isolation (Lock Off)

Lock off the isolating device and attach a warning notice.

  • Use a lock-off device (MCB lock, handle lock, or padlock)
  • Attach a caution label: 'Danger — Do Not Switch On'
  • Keep the key/unique lock on your person at all times
  • If lock-off not possible, remove fuse and keep it
  • For multiple workers: use a multi-lock hasp — each person applies their own padlock
4Prove the Test Instrument

Test your voltage indicator on a known live source to confirm it is working correctly.

  • Use a GS38-compliant two-pole voltage indicator (not a multimeter)
  • Test on a known live supply or a dedicated electronic proving unit
  • Confirm the indicator shows voltage correctly across all ranges
  • Check leads, probes, and batteries are in good condition
5Test for Dead

Test between all conductors and earth at the point of work to confirm the circuit is dead.

  • Single-phase: test Line–Neutral, Line–Earth, Neutral–Earth (3 tests)
  • Three-phase: complete the full 10-point test sequence (see below)
  • Test at the point of work, not just the DB
  • Also test at the point of isolation (outgoing side)
6Re-prove the Test Instrument

Test your voltage indicator again on a known live source to confirm it is still working.

  • Re-test on the same known live source used in Step 4
  • Confirm the indicator still reads voltage correctly
  • This proves the dead reading in Step 5 was genuine
  • If the indicator fails to light, treat the dead reading as invalid and repeat the entire process

“Prove — Test — Re-prove”

The golden rule: prove your tester works, test for dead, then prove your tester again.

Three-Phase 10-Point Test Sequence

All 10 Tests Required for 3-Phase Isolation

Missing any single test is an AM2 exam “red line” failure

#TestPurpose
1L1 to L2Phase-to-phase potential
2L1 to L3Phase-to-phase potential
3L2 to L3Phase-to-phase potential
4L1 to NeutralPhase-to-neutral voltage
5L2 to NeutralPhase-to-neutral voltage
6L3 to NeutralPhase-to-neutral voltage
7L1 to EarthLine-to-ground isolation
8L2 to EarthLine-to-ground isolation
9L3 to EarthLine-to-ground isolation
10Neutral to EarthConfirm neutral not floating/borrowed

GS38 Test Equipment Specifications

HSE Guidance Note GS38 — Test Equipment for Low Voltage Systems

Use a dedicated two-pole voltage indicator, not a multimeter. Multimeters are susceptible to wrong range selection, and a flat battery can give a false “zero” reading on a live circuit.

RequirementSpecificationRationale
Exposed metal tip≤4mm (preferably ≤2mm)Prevents accidental short-circuits between phases
Finger barriersMandatory on all probesPrevents hand sliding onto live conductors
Lead ratingCAT III or CAT IVWithstands high-energy voltage transients
Fusing (multimeters)HBC fuse (usually 500mA)Protects user if meter fails internally
Lead typeCaptive leads (non-detachable)Prevents exposing live connector pins

EAWR 1989 — Key Regulations

RegulationFocusApplication
Regulation 12Means for isolationIdentifying and operating the correct switch-disconnector or fuse
Regulation 13Precautions for dead workApplying personal padlocks and danger tags to isolation points
Regulation 14Live work prohibitionMandatory proving dead before touching any conductive part
Regulation 16CompetenceOperative must have skill to use GS38 equipment correctly
Ghost / Phantom Voltages

Isolated conductors running parallel to live conductors can pick up induced (“phantom”) voltages — enough to light up a voltage indicator but typically lacking current capacity for a direct shock.

Solution: Use a dual-impedance voltage indicator (e.g., Drummond MTL20) with a low-impedance test button. If the reading collapses to zero under load, it was induced. If it persists, there is a hard voltage source — stop work and investigate.

Common Mistakes
  • Skipping the re-prove step — the tester could have failed between tests
  • Testing at the DB only — always test at the point of work
  • Using a non-contact voltage detector alone — NCVDs are for initial checks only
  • Using a multimeter — use a dedicated two-pole voltage indicator (GS38)
  • Not locking off — a 2024 survey found 25% of electricians rarely or never lock off
  • Using tape to “secure” a breaker — provides no physical barrier to reconnection
  • Forgetting other supplies — check for UPS, generators, PV, battery storage
  • Testing on the incoming side — this side remains live after isolation
AM2 Exam — Automatic Fail Points

These “red line” errors result in immediate failure of the AM2 practical assessment

  • Failure to keep padlock key in personal possession
  • Failing to prove tester on proving unit both before AND after the circuit test
  • Testing on the incoming (live) side of the isolator
  • Missing a single test point in the 10-point three-phase sequence
  • Failure to attach a 'Danger: Men Working' notice

Built by Taro Schenker · Need a website for your trade business? Get in touch