Skip to content

Insulation Resistance Testing

Minimum IR values, test procedure, temperature correction, and material types

BS 7671 Reg 643.3, Table 64.1 & IET Guidance Note 3

What is Insulation Resistance Testing?

IR testing checks that cable insulation can safely contain the operating voltage. A DC test voltage is applied between conductors and between conductors and earth. The result is measured in megohms (MΩ) — higher is better. DC is used to eliminate capacitive reactance, giving a true resistive measurement.

Minimum IR Values (Table 64.1)

Circuit VoltageTest VoltageMinimum IRNote
SELV and PELV250V DC≥ 0.5 MΩExtra-low voltage circuits
Up to and including 500V (incl. FELV)500V DC≥ 1.0 MΩMost domestic/commercial — 230 V / 400 V
Above 500V up to 1000V1000V DC≥ 1.0 MΩHigher voltage systems

2 MΩ Investigation Threshold

While 1.0 MΩ is the regulatory pass, the HSE and Guidance Note 3 recommend that any reading below 2.0 MΩ on an individual circuit warrants further investigation. For new installations, a reading near the minimum usually indicates cable damage or moisture ingress during construction.

Test Procedure

1

Isolate and Lock Off

Safely isolate the circuit. Follow safe isolation procedure.

2

Disconnect Sensitive Equipment

Remove RCDs, dimmers, PIR sensors, LED drivers, SPDs, and any electronics. The 500 V DC test can damage them.

3

Set All Switches to ON

Turn on all light switches, FCUs, and isolators so the test covers all wiring including switch wires.

4

Remove Lamps and Accessories

Remove lamps (especially LEDs/CFLs). Disconnect accessories that may give false low readings.

5

Select Correct Test Voltage

Set the IR tester to the correct DC voltage for the circuit (usually 500 V DC for 230 V circuits).

6

Test Between Conductors

Test L–N, L–E, and N–E. For three-phase: each phase to every other phase, each phase to N, and each phase to E.

7

Record & Discharge

Record the reading in MΩ. Keep leads connected after releasing the test button to safely discharge cable capacitance.

SPD & PME Considerations

SPDs (Surge Protection)

SPDs activate on voltage transients — a 500 V DC test will trigger them, shunting current to earth and giving a false low reading.

Options:

  • - Disconnect SPDs before testing
  • - Connect L and N together, test against E (no potential across SPD)
  • - Reduce test voltage to 250 V DC (min 1.0 MΩ still applies)
PME (TN-C-S) N–E Trap

If the neutral is not isolated from the supply before testing, the tester measures the N–E bond at the source — giving a near-zero reading.

Solution: remove the neutral link at the origin or use a 4-pole isolation switch before testing N–E insulation resistance.

Interpreting Results

Typical IR Readings for 230 V Circuits
ReadingIndicationNotes
> 200 MΩExcellentNew installation or very good condition
50–200 MΩGoodNormal for an installation in good condition
2–50 MΩAcceptableOlder installation — monitor on future inspections
1–2 MΩMarginalHSE/GN3 recommend investigation below 2 MΩ
< 1 MΩFailBelow minimum — investigate and rectify before energising

Temperature Correction to 20 °C

PVC insulation resistance halves for every 10 °C rise. Multiply the measured value by the factor below to normalise readings to 20 °C for trending.

Temperature (°C)Multiplier to Correct to 20 °C
10 °C0.50
15 °C0.71
20 °C1.00
25 °C1.41
30 °C2.00
35 °C2.82
40 °C4.00

Insulation Material Types

MaterialTypeMax TempFailure Symptoms
PVCThermoplastic70 °CEmbrittlement, plasticiser migration, 'green goo' on copper
XLPEThermoset90 °CRarely fails unless mechanical damage — gigaohm-range readings
VRI (Rubber)Thermoset60 °CCracking, powdering, moisture absorption — pre-1960s
EPRThermoset90 °CRetains flexibility, ozone-resistant — industrial use

Factors Affecting Insulation Resistance

FactorEffect
Moisture / dampDramatically lowers IR. Common after flooding or in unheated buildings.
Age of installationInsulation degrades over time. Older wiring will have lower readings.
Cable lengthIR is inversely proportional to length — runs >250 m naturally read lower.
TemperaturePVC IR halves for every 10 °C rise. Use the correction table below.
Humidity > 70%Moisture film on terminations creates surface leakage paths — not bulk insulation failure.
Number of outletsMore accessories = more parallel leakage paths. Isolate suspect circuits.
Connected equipmentElectronics, heaters, motors give false low readings if not disconnected.

EICR Classification for IR Observations

ConditionCode
Insulation completely failed, exposed live partsC1
IR result below minimum on a circuitC2
IR result between minimum and 2 MΩC3
Aged VRI passing tests but showing degradationC3
Result influenced by loads that cannot be disconnectedFI

Important Warnings

  • - Disconnect electronic equipment before testing — 500 V DC destroys RCDs, dimmers, LED drivers, PIRs
  • - Never IR test a live circuit — follow safe isolation procedure first
  • - Discharge capacitance — keep leads connected after releasing the test button; long cables store charge
  • - Whole-board test: all circuits in parallel = total IR lower than any individual circuit. If below 1 MΩ, test circuits individually
  • - Record exact values (not ">200") to allow future inspectors to identify deterioration trends

Key Points

  • - Minimum applies to each individual circuit, not the whole installation
  • - Test between all live conductors and earth: L–E, N–E, and L–N
  • - IR is the second dead test — performed after continuity of protective conductors
  • - FELV circuits are tested at 500 V DC (not 250 V) — they lack full separation from LV
  • - For occupied premises (EICR), a global test at 250 V DC with L and N linked minimises risk to hidden electronics
  • - VRI (pre-1960s rubber) may pass but crumbles when disturbed — treat as C3 minimum

Built by Taro Schenker · Need a website for your trade business? Get in touch