Max Zs for 20A Type B MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
2.19Ω
Testing Limit
1.75Ω
Max Zs (5s)
2.19Ω
Ia (0.4s)
100A
At a Glance
- Device
- MCB Type B — 20A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 2.19Ω
- Max Zs (5s)
- 2.19Ω
- Testing Limit (80%)
- 1.75Ω
- Ia (0.4s)
- 100A
About MCB Type B
Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.
Typical Circuits for 20A Type B MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Radial socket circuit | 2.5–4.0mm² T&E | Larger floor area |
| Water heater | 2.5mm² T&E | Up to 4.6kW |
Worked Example: Maximum Cable Run for 20A MCB Type B
- Maximum Zs (tabulated) = 2.19Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 2.19 × 0.8 = 1.75Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 1.75 − 0.35 = 1.4Ω
- Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
- Maximum cable run = 1.4 ÷ 0.01482 = 94.5m
On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 94.5m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s and 5s Disconnection — Same Values for Type B
For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 2.19Ω for both disconnection times at 20A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).
20A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 2.19Ω | 1.75Ω |
| MCB Type C | 1.09Ω | 0.87Ω |
| MCB Type D | 0.55Ω | 0.44Ω |
| BS 88 Fuse | 1.84Ω | 1.47Ω |
| BS 1361 Fuse | 2.42Ω | 1.94Ω |
| BS 3036 Semi-enclosed Fuse | 2.14Ω | 1.71Ω |