Max Zs for 16A Type B MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

2.73Ω

Testing Limit

2.18Ω

Max Zs (5s)

2.73Ω

Ia (0.4s)

80A

At a Glance

Device
MCB Type B16A
Standard
BS EN 60898
Max Zs (0.4s)
2.73Ω
Max Zs (5s)
2.73Ω
Testing Limit (80%)
2.18Ω
Ia (0.4s)
80A

About MCB Type B

Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.

Typical Circuits for 16A Type B MCB

Recommended cable sizes for 16A Type B MCB circuits
CircuitCable SizeNotes
Radial socket circuit2.5mm² T&EUp to 20m² floor area
Towel rail / small heater2.5mm² T&EDedicated supply

Worked Example: Maximum Cable Run for 16A MCB Type B

  1. Maximum Zs (tabulated) = 2.73Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 2.73 × 0.8 = 2.18Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 2.18 − 0.35 = 1.83Ω
  5. Using 2.5mm² T&E: R1+R2 = 14.82 mΩ/m
  6. Maximum cable run = 1.83 ÷ 0.01482 = 123.5m

On a TN-C-S (PME) supply with 2.5mm² cable, the maximum one-way cable run is approximately 123.5m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s and 5s Disconnection — Same Values for Type B

For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 2.73Ω for both disconnection times at 16A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).

16A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B2.73Ω2.18Ω
MCB Type C1.37Ω1.1Ω
MCB Type D0.68Ω0.54Ω
BS 88 Fuse2.42Ω1.94Ω

Frequently Asked Questions