Max Zs for 10A Type B MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
4.37Ω
Testing Limit
3.5Ω
Max Zs (5s)
4.37Ω
Ia (0.4s)
50A
At a Glance
- Device
- MCB Type B — 10A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 4.37Ω
- Max Zs (5s)
- 4.37Ω
- Testing Limit (80%)
- 3.5Ω
- Ia (0.4s)
- 50A
About MCB Type B
Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.
Typical Circuits for 10A Type B MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Lighting circuit (larger) | 1.0–1.5mm² T&E | Extended runs or higher wattage |
| Immersion heater (small) | 1.5mm² T&E | Up to 2.4kW |
Worked Example: Maximum Cable Run for 10A MCB Type B
- Maximum Zs (tabulated) = 4.37Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 4.37 × 0.8 = 3.5Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 3.5 − 0.35 = 3.15Ω
- Using 1.5mm² T&E: R1+R2 = 24.2 mΩ/m
- Maximum cable run = 3.15 ÷ 0.0242 = 130.2m
On a TN-C-S (PME) supply with 1.5mm² cable, the maximum one-way cable run is approximately 130.2m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s and 5s Disconnection — Same Values for Type B
For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 4.37Ω for both disconnection times at 10A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).
10A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 4.37Ω | 3.5Ω |
| MCB Type C | 2.19Ω | 1.75Ω |
| MCB Type D | 1.09Ω | 0.87Ω |