Max Zs for 10A BS 88 Fuse
BS 7671 Table 41.4 — BS 7671:2018+A2:2022
Max Zs (0.4s)
4.85Ω
Testing Limit
3.88Ω
Max Zs (5s)
7.04Ω
Ia (0.4s)
45A
At a Glance
- Device
- BS 88 Fuse — 10A
- Standard
- BS 88
- Max Zs (0.4s)
- 4.85Ω
- Max Zs (5s)
- 7.04Ω
- Testing Limit (80%)
- 3.88Ω
- Ia (0.4s)
- 45A
About BS 88 Fuse
BS 88 fuses (also called HRC or HBC fuses) are high breaking capacity industrial fuses. They protect distribution board sub-circuits and main incomers. Their time/current characteristics differ from MCBs — disconnection time depends on the precise fault current level, not a fixed multiplier.
Worked Example: Maximum Cable Run for 10A BS 88 Fuse
- Maximum Zs (tabulated) = 4.85Ω (BS 7671 Table 41.4)
- Testing limit (80%) = 4.85 × 0.8 = 3.88Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 3.88 − 0.35 = 3.53Ω
- Using 1.5mm² T&E: R1+R2 = 24.2 mΩ/m
- Maximum cable run = 3.53 ÷ 0.0242 = 145.9m
On a TN-C-S (PME) supply with 1.5mm² cable, the maximum one-way cable run is approximately 145.9m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection Times
Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 10A: max Zs = 4.85Ω (0.4s) vs 7.04Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 4.85Ω | 3.88Ω |
| 5 seconds | 7.04Ω | 5.63Ω |
10A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 4.37Ω | 3.5Ω |
| MCB Type C | 2.19Ω | 1.75Ω |
| MCB Type D | 1.09Ω | 0.87Ω |
| BS 88 Fuse | 4.85Ω | 3.88Ω |