Skip to content

Max Zs for 10A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

2.19Ω

Testing Limit

1.75Ω

Max Zs (5s)

2.19Ω

Ia (0.4s)

100A

At a Glance

Device
MCB Type C10A
Standard
BS EN 60898
Max Zs (0.4s)
2.19Ω
Max Zs (5s)
2.19Ω
Testing Limit (80%)
1.75Ω
Ia (0.4s)
100A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 10A Type C MCB

Recommended cable sizes for 10A Type C MCB circuits
CircuitCable SizeNotes
Fluorescent lighting1.5mm²Discharge lighting with high inrush

Worked Example: Maximum Cable Run for 10A MCB Type C

  1. Maximum Zs (tabulated) = 2.19Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 2.19 × 0.8 = 1.75Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 1.75 − 0.35 = 1.4Ω
  5. Using 1.5mm² T&E: R1+R2 = 24.2 mΩ/m
  6. Maximum cable run = 1.4 ÷ 0.0242 = 57.9m

On a TN-C-S (PME) supply with 1.5mm² cable, the maximum one-way cable run is approximately 57.9m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Different Values for Type C

At 10A, the max Zs values are the same for both disconnection times: 2.19Ω.

10A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B4.37Ω3.5Ω
MCB Type C2.19Ω1.75Ω
MCB Type D1.09Ω0.87Ω
BS 88 Fuse4.85Ω3.88Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch