Skip to content

Max Zs for 6A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

3.64Ω

Testing Limit

2.91Ω

Max Zs (5s)

3.64Ω

Ia (0.4s)

60A

At a Glance

Device
MCB Type C6A
Standard
BS EN 60898
Max Zs (0.4s)
3.64Ω
Max Zs (5s)
3.64Ω
Testing Limit (80%)
2.91Ω
Ia (0.4s)
60A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 6A Type C MCB

Recommended cable sizes for 6A Type C MCB circuits
CircuitCable SizeNotes
Small motor circuit1.0mm²Fan motors, small pumps with high inrush

Worked Example: Maximum Cable Run for 6A MCB Type C

  1. Maximum Zs (tabulated) = 3.64Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 3.64 × 0.8 = 2.91Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 2.91 − 0.35 = 2.56Ω
  5. Using 1mm² T&E: R1+R2 = 36.2 mΩ/m
  6. Maximum cable run = 2.56 ÷ 0.0362 = 70.7m

On a TN-C-S (PME) supply with 1mm² cable, the maximum one-way cable run is approximately 70.7m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Different Values for Type C

At 6A, the max Zs values are the same for both disconnection times: 3.64Ω.

6A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B7.28Ω5.82Ω
MCB Type C3.64Ω2.91Ω
MCB Type D1.82Ω1.46Ω
BS 88 Fuse8.09Ω6.47Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch