Skip to content

Max Zs for 6A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

3.64Ω

Testing Limit

2.91Ω

Max Zs (5s)

7.28Ω

Ia (0.4s)

60A

At a Glance

Device
MCB Type C6A
Standard
BS EN 60898
Max Zs (0.4s)
3.64Ω
Max Zs (5s)
7.28Ω
Testing Limit (80%)
2.91Ω
Ia (0.4s)
60A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 6A Type C MCB

Recommended cable sizes for 6A Type C MCB circuits
CircuitCable SizeNotes
Small motor circuit1.0mm²Fan motors, small pumps with high inrush

Worked Example: Maximum Cable Run for 6A MCB Type C

  1. Maximum Zs (tabulated) = 3.64Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 3.64 × 0.8 = 2.91Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 2.91 − 0.35 = 2.56Ω
  5. Using 1mm² T&E: R1+R2 = 36.2 mΩ/m
  6. Maximum cable run = 2.56 ÷ 0.0362 = 70.7m

On a TN-C-S (PME) supply with 1mm² cable, the maximum one-way cable run is approximately 70.7m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Different Values for Type C

Type C MCBs require 10× In for 0.4s disconnection but only 5× In for 5s. At 6A: max Zs = 3.64Ω (0.4s) vs 7.28Ω (5s). For distribution circuits (5s allowed), you have nearly double the impedance budget. Final circuits serving socket outlets must still meet the 0.4s limit.

Disconnection TimeMax ZsTesting Limit (80%)
0.4 seconds3.64Ω2.91Ω
5 seconds7.28Ω5.82Ω

6A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B7.28Ω5.82Ω
MCB Type C3.64Ω2.91Ω
MCB Type D1.82Ω1.46Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch