Max Zs for 6A Type C MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
3.64Ω
Testing Limit
2.91Ω
Max Zs (5s)
7.28Ω
Ia (0.4s)
60A
At a Glance
- Device
- MCB Type C — 6A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 3.64Ω
- Max Zs (5s)
- 7.28Ω
- Testing Limit (80%)
- 2.91Ω
- Ia (0.4s)
- 60A
About MCB Type C
Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.
Typical Circuits for 6A Type C MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Small motor circuit | 1.0mm² | Fan motors, small pumps with high inrush |
Worked Example: Maximum Cable Run for 6A MCB Type C
- Maximum Zs (tabulated) = 3.64Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 3.64 × 0.8 = 2.91Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 2.91 − 0.35 = 2.56Ω
- Using 1mm² T&E: R1+R2 = 36.2 mΩ/m
- Maximum cable run = 2.56 ÷ 0.0362 = 70.7m
On a TN-C-S (PME) supply with 1mm² cable, the maximum one-way cable run is approximately 70.7m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection — Different Values for Type C
Type C MCBs require 10× In for 0.4s disconnection but only 5× In for 5s. At 6A: max Zs = 3.64Ω (0.4s) vs 7.28Ω (5s). For distribution circuits (5s allowed), you have nearly double the impedance budget. Final circuits serving socket outlets must still meet the 0.4s limit.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 3.64Ω | 2.91Ω |
| 5 seconds | 7.28Ω | 5.82Ω |
6A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 7.28Ω | 5.82Ω |
| MCB Type C | 3.64Ω | 2.91Ω |
| MCB Type D | 1.82Ω | 1.46Ω |