Skip to content

Max Zs for 6A Type D MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

1.82Ω

Testing Limit

1.46Ω

Max Zs (5s)

1.82Ω

Ia (0.4s)

120A

At a Glance

Device
MCB Type D6A
Standard
BS EN 60898
Max Zs (0.4s)
1.82Ω
Max Zs (5s)
1.82Ω
Testing Limit (80%)
1.46Ω
Ia (0.4s)
120A

About MCB Type D

Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.

Worked Example: Maximum Cable Run for 6A MCB Type D

  1. Maximum Zs (tabulated) = 1.82Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 1.82 × 0.8 = 1.46Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 1.46 − 0.35 = 1.11Ω
  5. Using 1mm² T&E: R1+R2 = 36.2 mΩ/m
  6. Maximum cable run = 1.11 ÷ 0.0362 = 30.7m

On a TN-C-S (PME) supply with 1mm² cable, the maximum one-way cable run is approximately 30.7m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Significant Difference for Type D

At 6A, the max Zs values for Type D are 1.82Ω for both disconnection times.

6A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B7.28Ω5.82Ω
MCB Type C3.64Ω2.91Ω
MCB Type D1.82Ω1.46Ω
BS 88 Fuse8.09Ω6.47Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch