Max Zs for 6A Type D MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
1.82Ω
Testing Limit
1.46Ω
Max Zs (5s)
3.64Ω
Ia (0.4s)
120A
At a Glance
- Device
- MCB Type D — 6A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 1.82Ω
- Max Zs (5s)
- 3.64Ω
- Testing Limit (80%)
- 1.46Ω
- Ia (0.4s)
- 120A
About MCB Type D
Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.
Worked Example: Maximum Cable Run for 6A MCB Type D
- Maximum Zs (tabulated) = 1.82Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 1.82 × 0.8 = 1.46Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 1.46 − 0.35 = 1.11Ω
- Using 1mm² T&E: R1+R2 = 36.2 mΩ/m
- Maximum cable run = 1.11 ÷ 0.0362 = 30.7m
On a TN-C-S (PME) supply with 1mm² cable, the maximum one-way cable run is approximately 30.7m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection — Significant Difference for Type D
Type D MCBs require 20× In for 0.4s but only 10× In for 5s. At 6A: max Zs = 1.82Ω (0.4s) vs 3.64Ω (5s). The 5s value is exactly double. This is why Type D MCBs are mainly used on distribution circuits where 5s disconnection is acceptable.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 1.82Ω | 1.46Ω |
| 5 seconds | 3.64Ω | 2.91Ω |
6A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 7.28Ω | 5.82Ω |
| MCB Type C | 3.64Ω | 2.91Ω |
| MCB Type D | 1.82Ω | 1.46Ω |