Max Zs for 6A Type B MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
7.28Ω
Testing Limit
5.82Ω
Max Zs (5s)
7.28Ω
Ia (0.4s)
30A
At a Glance
- Device
- MCB Type B — 6A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 7.28Ω
- Max Zs (5s)
- 7.28Ω
- Testing Limit (80%)
- 5.82Ω
- Ia (0.4s)
- 30A
About MCB Type B
Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.
Typical Circuits for 6A Type B MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Lighting circuit | 1.0mm² T&E | Up to 12 points per circuit |
| Low-power LED lighting | 1.0mm² T&E | Common in modern domestic installs |
Worked Example: Maximum Cable Run for 6A MCB Type B
- Maximum Zs (tabulated) = 7.28Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 7.28 × 0.8 = 5.82Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 5.82 − 0.35 = 5.47Ω
- Using 1mm² T&E: R1+R2 = 36.2 mΩ/m
- Maximum cable run = 5.47 ÷ 0.0362 = 151.1m
On a TN-C-S (PME) supply with 1mm² cable, the maximum one-way cable run is approximately 151.1m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s and 5s Disconnection — Same Values for Type B
For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 7.28Ω for both disconnection times at 6A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).
6A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 7.28Ω | 5.82Ω |
| MCB Type C | 3.64Ω | 2.91Ω |
| MCB Type D | 1.82Ω | 1.46Ω |