Skip to content

Max Zs for 6A Type B MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

7.28Ω

Testing Limit

5.82Ω

Max Zs (5s)

7.28Ω

Ia (0.4s)

30A

At a Glance

Device
MCB Type B6A
Standard
BS EN 60898
Max Zs (0.4s)
7.28Ω
Max Zs (5s)
7.28Ω
Testing Limit (80%)
5.82Ω
Ia (0.4s)
30A

About MCB Type B

Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.

Typical Circuits for 6A Type B MCB

Recommended cable sizes for 6A Type B MCB circuits
CircuitCable SizeNotes
Lighting circuit1.0mm² T&EUp to 12 points per circuit
Low-power LED lighting1.0mm² T&ECommon in modern domestic installs

Worked Example: Maximum Cable Run for 6A MCB Type B

  1. Maximum Zs (tabulated) = 7.28Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 7.28 × 0.8 = 5.82Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 5.82 − 0.35 = 5.47Ω
  5. Using 1mm² T&E: R1+R2 = 36.2 mΩ/m
  6. Maximum cable run = 5.47 ÷ 0.0362 = 151.1m

On a TN-C-S (PME) supply with 1mm² cable, the maximum one-way cable run is approximately 151.1m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s and 5s Disconnection — Same Values for Type B

For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 7.28Ω for both disconnection times at 6A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).

6A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B7.28Ω5.82Ω
MCB Type C3.64Ω2.91Ω
MCB Type D1.82Ω1.46Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch