Max Zs for 6A BS 88 Fuse
BS 7671 Table 41.4 — BS 7671:2018+A2:2022
Max Zs (0.4s)
8.09Ω
Testing Limit
6.47Ω
Max Zs (5s)
12.84Ω
Ia (0.4s)
27A
At a Glance
- Device
- BS 88 Fuse — 6A
- Standard
- BS 88
- Max Zs (0.4s)
- 8.09Ω
- Max Zs (5s)
- 12.84Ω
- Testing Limit (80%)
- 6.47Ω
- Ia (0.4s)
- 27A
About BS 88 Fuse
BS 88 fuses (also called HRC or HBC fuses) are high breaking capacity industrial fuses. They protect distribution board sub-circuits and main incomers. Their time/current characteristics differ from MCBs — disconnection time depends on the precise fault current level, not a fixed multiplier.
Worked Example: Maximum Cable Run for 6A BS 88 Fuse
- Maximum Zs (tabulated) = 8.09Ω (BS 7671 Table 41.4)
- Testing limit (80%) = 8.09 × 0.8 = 6.47Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 6.47 − 0.35 = 6.12Ω
- Using 1.5mm² T&E: R1+R2 = 24.2 mΩ/m
- Maximum cable run = 6.12 ÷ 0.0242 = 252.9m
On a TN-C-S (PME) supply with 1.5mm² cable, the maximum one-way cable run is approximately 252.9m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection Times
Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 6A: max Zs = 8.09Ω (0.4s) vs 12.84Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 8.09Ω | 6.47Ω |
| 5 seconds | 12.84Ω | 10.27Ω |
6A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 7.28Ω | 5.82Ω |
| MCB Type C | 3.64Ω | 2.91Ω |
| MCB Type D | 1.82Ω | 1.46Ω |
| BS 88 Fuse | 8.09Ω | 6.47Ω |