Max Zs for 10A Type D MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
1.09Ω
Testing Limit
0.87Ω
Max Zs (5s)
2.19Ω
Ia (0.4s)
200A
At a Glance
- Device
- MCB Type D — 10A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 1.09Ω
- Max Zs (5s)
- 2.19Ω
- Testing Limit (80%)
- 0.87Ω
- Ia (0.4s)
- 200A
About MCB Type D
Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.
Typical Circuits for 10A Type D MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| X-ray equipment | 1.5–2.5mm² | Very high inrush medical equipment |
Worked Example: Maximum Cable Run for 10A MCB Type D
- Maximum Zs (tabulated) = 1.09Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 1.09 × 0.8 = 0.87Ω
- Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
- Maximum R1+R2 = 0.87 − 0.35 = 0.52Ω
- Using 1.5mm² T&E: R1+R2 = 24.2 mΩ/m
- Maximum cable run = 0.52 ÷ 0.0242 = 21.5m
On a TN-C-S (PME) supply with 1.5mm² cable, the maximum one-way cable run is approximately 21.5m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.
0.4s vs 5s Disconnection — Significant Difference for Type D
Type D MCBs require 20× In for 0.4s but only 10× In for 5s. At 10A: max Zs = 1.09Ω (0.4s) vs 2.19Ω (5s). The 5s value is exactly double. This is why Type D MCBs are mainly used on distribution circuits where 5s disconnection is acceptable.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 1.09Ω | 0.87Ω |
| 5 seconds | 2.19Ω | 1.75Ω |
10A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 4.37Ω | 3.5Ω |
| MCB Type C | 2.19Ω | 1.75Ω |
| MCB Type D | 1.09Ω | 0.87Ω |