Max Zs for 10A Type D MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

1.09Ω

Testing Limit

0.87Ω

Max Zs (5s)

1.09Ω

Ia (0.4s)

200A

At a Glance

Device
MCB Type D10A
Standard
BS EN 60898
Max Zs (0.4s)
1.09Ω
Max Zs (5s)
1.09Ω
Testing Limit (80%)
0.87Ω
Ia (0.4s)
200A

About MCB Type D

Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.

Typical Circuits for 10A Type D MCB

Recommended cable sizes for 10A Type D MCB circuits
CircuitCable SizeNotes
X-ray equipment1.5–2.5mm²Very high inrush medical equipment

Worked Example: Maximum Cable Run for 10A MCB Type D

  1. Maximum Zs (tabulated) = 1.09Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 1.09 × 0.8 = 0.87Ω
  3. Assume Ze = 0.35Ω (typical TN-C-S (PME) supply)
  4. Maximum R1+R2 = 0.87 − 0.35 = 0.52Ω
  5. Using 1.5mm² T&E: R1+R2 = 24.2 mΩ/m
  6. Maximum cable run = 0.52 ÷ 0.0242 = 21.5m

On a TN-C-S (PME) supply with 1.5mm² cable, the maximum one-way cable run is approximately 21.5m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s vs 5s Disconnection — Significant Difference for Type D

At 10A, the max Zs values for Type D are 1.09Ω for both disconnection times.

10A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B4.37Ω3.5Ω
MCB Type C2.19Ω1.75Ω
MCB Type D1.09Ω0.87Ω
BS 88 Fuse4.85Ω3.88Ω