Max Zs for 63A Type D MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.17Ω

Testing Limit

0.14Ω

Max Zs (5s)

0.17Ω

Ia (0.4s)

1260A

At a Glance

Device
MCB Type D63A
Standard
BS EN 60898
Max Zs (0.4s)
0.17Ω
Max Zs (5s)
0.17Ω
Testing Limit (80%)
0.14Ω
Ia (0.4s)
1260A

About MCB Type D

Type D MCBs trip magnetically at 10–20× In. They handle the highest inrush currents — transformers, welding equipment, and X-ray machines. The very high trip multiplier produces very low max Zs values, which severely limits cable run lengths. Type D devices are rarely suitable for final circuits with 0.4s disconnection requirements.

Typical Circuits for 63A Type D MCB

Recommended cable sizes for 63A Type D MCB circuits
CircuitCable SizeNotes
Large transformer bank16mm²Industrial transformer primary protection

Worked Example: Maximum Cable Run for 63A MCB Type D

  1. Maximum Zs (tabulated) = 0.17Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.17 × 0.8 = 0.14Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.14 − 0.8 = —Ω
  5. Using 16mm² T&E: R1+R2 = 2.3 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s vs 5s Disconnection — Significant Difference for Type D

At 63A, the max Zs values for Type D are 0.17Ω for both disconnection times.

63A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.69Ω0.55Ω
MCB Type C0.35Ω0.28Ω
MCB Type D0.17Ω0.14Ω
BS 88 Fuse0.43Ω0.34Ω

Frequently Asked Questions