Max Zs for 63A Type B MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
0.69Ω
Testing Limit
0.55Ω
Max Zs (5s)
0.69Ω
Ia (0.4s)
315A
At a Glance
- Device
- MCB Type B — 63A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 0.69Ω
- Max Zs (5s)
- 0.69Ω
- Testing Limit (80%)
- 0.55Ω
- Ia (0.4s)
- 315A
About MCB Type B
Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.
Typical Circuits for 63A Type B MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Sub-main to outbuilding | 16mm² T&E or SWA | Distribution board sub-feed |
| EV charger (large) | 10–16mm² T&E | 22kW three-phase charger protection |
Worked Example: Maximum Cable Run for 63A MCB Type B
- Maximum Zs (tabulated) = 0.69Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 0.69 × 0.8 = 0.55Ω
- Assume Ze = 0.8Ω (typical TN-S supply)
- Maximum R1+R2 = 0.55 − 0.8 = —Ω
- Using 16mm² T&E: R1+R2 = 2.3 mΩ/m
- The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.
The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.
0.4s and 5s Disconnection — Same Values for Type B
For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 0.69Ω for both disconnection times at 63A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).
63A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 0.69Ω | 0.55Ω |
| MCB Type C | 0.35Ω | 0.28Ω |
| MCB Type D | 0.17Ω | 0.14Ω |
| BS 88 Fuse | 0.54Ω | 0.43Ω |