Max Zs for 50A Type B MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.87Ω

Testing Limit

0.7Ω

Max Zs (5s)

0.87Ω

Ia (0.4s)

250A

At a Glance

Device
MCB Type B50A
Standard
BS EN 60898
Max Zs (0.4s)
0.87Ω
Max Zs (5s)
0.87Ω
Testing Limit (80%)
0.7Ω
Ia (0.4s)
250A

About MCB Type B

Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.

Typical Circuits for 50A Type B MCB

Recommended cable sizes for 50A Type B MCB circuits
CircuitCable SizeNotes
Electric shower (10.5–11kW)10mm² T&EDedicated radial supply
Large cooker10mm² T&ERange cooker with multiple ovens

Worked Example: Maximum Cable Run for 50A MCB Type B

  1. Maximum Zs (tabulated) = 0.87Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.87 × 0.8 = 0.7Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.7 − 0.8 = —Ω
  5. Using 10mm² T&E: R1+R2 = 3.66 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s and 5s Disconnection — Same Values for Type B

For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 0.87Ω for both disconnection times at 50A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).

50A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.87Ω0.7Ω
MCB Type C0.44Ω0.35Ω
MCB Type D0.22Ω0.18Ω
BS 88 Fuse0.68Ω0.54Ω

Frequently Asked Questions