Max Zs for 50A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.44Ω

Testing Limit

0.35Ω

Max Zs (5s)

0.87Ω

Ia (0.4s)

500A

At a Glance

Device
MCB Type C50A
Standard
BS EN 60898
Max Zs (0.4s)
0.44Ω
Max Zs (5s)
0.87Ω
Testing Limit (80%)
0.35Ω
Ia (0.4s)
500A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 50A Type C MCB

Recommended cable sizes for 50A Type C MCB circuits
CircuitCable SizeNotes
Large industrial motor10mm²Heavier workshop or factory plant

Worked Example: Maximum Cable Run for 50A MCB Type C

  1. Maximum Zs (tabulated) = 0.44Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.44 × 0.8 = 0.35Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.35 − 0.8 = —Ω
  5. Using 10mm² T&E: R1+R2 = 3.66 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s vs 5s Disconnection — Different Values for Type C

Type C MCBs require 10× In for 0.4s disconnection but only 5× In for 5s. At 50A: max Zs = 0.44Ω (0.4s) vs 0.87Ω (5s). For distribution circuits (5s allowed), you have nearly double the impedance budget. Final circuits serving socket outlets must still meet the 0.4s limit.

Disconnection TimeMax ZsTesting Limit (80%)
0.4 seconds0.44Ω0.35Ω
5 seconds0.87Ω0.7Ω

50A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.87Ω0.7Ω
MCB Type C0.44Ω0.35Ω
MCB Type D0.22Ω0.18Ω
BS 88 Fuse0.68Ω0.54Ω

Frequently Asked Questions