Max Zs for 50A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.44Ω

Testing Limit

0.35Ω

Max Zs (5s)

0.44Ω

Ia (0.4s)

500A

At a Glance

Device
MCB Type C50A
Standard
BS EN 60898
Max Zs (0.4s)
0.44Ω
Max Zs (5s)
0.44Ω
Testing Limit (80%)
0.35Ω
Ia (0.4s)
500A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Typical Circuits for 50A Type C MCB

Recommended cable sizes for 50A Type C MCB circuits
CircuitCable SizeNotes
Large industrial motor10mm²Heavier workshop or factory plant

Worked Example: Maximum Cable Run for 50A MCB Type C

  1. Maximum Zs (tabulated) = 0.44Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.44 × 0.8 = 0.35Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.35 − 0.8 = —Ω
  5. Using 10mm² T&E: R1+R2 = 3.66 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s vs 5s Disconnection — Different Values for Type C

At 50A, the max Zs values are the same for both disconnection times: 0.44Ω.

50A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.87Ω0.7Ω
MCB Type C0.44Ω0.35Ω
MCB Type D0.22Ω0.18Ω
BS 88 Fuse0.57Ω0.46Ω