Max Zs for 50A BS 88 Fuse

BS 7671 Table 41.4 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.68Ω

Testing Limit

0.54Ω

Max Zs (5s)

1.4Ω

Ia (0.4s)

321A

At a Glance

Device
BS 88 Fuse50A
Standard
BS 88
Max Zs (0.4s)
0.68Ω
Max Zs (5s)
1.4Ω
Testing Limit (80%)
0.54Ω
Ia (0.4s)
321A

About BS 88 Fuse

BS 88 fuses (also called HRC or HBC fuses) are high breaking capacity industrial fuses. They protect distribution board sub-circuits and main incomers. Their time/current characteristics differ from MCBs — disconnection time depends on the precise fault current level, not a fixed multiplier.

Worked Example: Maximum Cable Run for 50A BS 88 Fuse

  1. Maximum Zs (tabulated) = 0.68Ω (BS 7671 Table 41.4)
  2. Testing limit (80%) = 0.68 × 0.8 = 0.54Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.54 − 0.8 = —Ω
  5. Using 16mm² T&E: R1+R2 = 2.3 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s vs 5s Disconnection Times

Fuse characteristics differ from MCBs — disconnection time depends on the time/current curve. At 50A: max Zs = 0.68Ω (0.4s) vs 1.4Ω (5s). The 5s value is higher because a lower fault current will still melt the fuse element given more time. Use the 0.4s value for final circuits and 5s for distribution circuits only.

Disconnection TimeMax ZsTesting Limit (80%)
0.4 seconds0.68Ω0.54Ω
5 seconds1.4Ω1.12Ω

50A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.87Ω0.7Ω
MCB Type C0.44Ω0.35Ω
MCB Type D0.22Ω0.18Ω
BS 88 Fuse0.68Ω0.54Ω

Frequently Asked Questions