Max Zs for 40A Type C MCB
BS 7671 Table 41.3 — BS 7671:2018+A2:2022
Max Zs (0.4s)
0.55Ω
Testing Limit
0.44Ω
Max Zs (5s)
1.09Ω
Ia (0.4s)
400A
At a Glance
- Device
- MCB Type C — 40A
- Standard
- BS EN 60898
- Max Zs (0.4s)
- 0.55Ω
- Max Zs (5s)
- 1.09Ω
- Testing Limit (80%)
- 0.44Ω
- Ia (0.4s)
- 400A
About MCB Type C
Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.
Typical Circuits for 40A Type C MCB
| Circuit | Cable Size | Notes |
|---|---|---|
| Industrial motor | 6.0–10mm² | Workshop machinery |
Worked Example: Maximum Cable Run for 40A MCB Type C
- Maximum Zs (tabulated) = 0.55Ω (BS 7671 Table 41.3)
- Testing limit (80%) = 0.55 × 0.8 = 0.44Ω
- Assume Ze = 0.8Ω (typical TN-S supply)
- Maximum R1+R2 = 0.44 − 0.8 = —Ω
- Using 6mm² T&E: R1+R2 = 6.16 mΩ/m
- The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.
The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.
0.4s vs 5s Disconnection — Different Values for Type C
Type C MCBs require 10× In for 0.4s disconnection but only 5× In for 5s. At 40A: max Zs = 0.55Ω (0.4s) vs 1.09Ω (5s). For distribution circuits (5s allowed), you have nearly double the impedance budget. Final circuits serving socket outlets must still meet the 0.4s limit.
| Disconnection Time | Max Zs | Testing Limit (80%) |
|---|---|---|
| 0.4 seconds | 0.55Ω | 0.44Ω |
| 5 seconds | 1.09Ω | 0.87Ω |
40A Across Device Types
| Device Type | Max Zs (0.4s) | Testing Limit |
|---|---|---|
| MCB Type B | 1.09Ω | 0.87Ω |
| MCB Type C | 0.55Ω | 0.44Ω |
| MCB Type D | 0.27Ω | 0.22Ω |
| BS 88 Fuse | 0.87Ω | 0.7Ω |