Max Zs for 40A Type B MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

1.09Ω

Testing Limit

0.87Ω

Max Zs (5s)

1.09Ω

Ia (0.4s)

200A

At a Glance

Device
MCB Type B40A
Standard
BS EN 60898
Max Zs (0.4s)
1.09Ω
Max Zs (5s)
1.09Ω
Testing Limit (80%)
0.87Ω
Ia (0.4s)
200A

About MCB Type B

Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.

Typical Circuits for 40A Type B MCB

Recommended cable sizes for 40A Type B MCB circuits
CircuitCable SizeNotes
Cooker circuit6.0mm² T&EUp to 9.2kW freestanding cooker
Electric shower (8.5kW)6.0mm² T&EShort runs only

Worked Example: Maximum Cable Run for 40A MCB Type B

  1. Maximum Zs (tabulated) = 1.09Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 1.09 × 0.8 = 0.87Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.87 − 0.8 = 0.07Ω
  5. Using 6mm² T&E: R1+R2 = 6.16 mΩ/m
  6. Maximum cable run = 0.07 ÷ 0.0061600000000000005 = 11.4m

On a TN-S supply with 6mm² cable, the maximum one-way cable run is approximately 11.4m before Zs exceeds the testing limit. In practice, always measure — parallel earth paths and cable route conditions will affect the actual value.

0.4s and 5s Disconnection — Same Values for Type B

For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 1.09Ω for both disconnection times at 40A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).

40A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B1.09Ω0.87Ω
MCB Type C0.55Ω0.44Ω
MCB Type D0.27Ω0.22Ω
BS 88 Fuse0.87Ω0.7Ω

Frequently Asked Questions