Max Zs for 80A Type B MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.55Ω

Testing Limit

0.44Ω

Max Zs (5s)

0.55Ω

Ia (0.4s)

400A

At a Glance

Device
MCB Type B80A
Standard
BS EN 60898
Max Zs (0.4s)
0.55Ω
Max Zs (5s)
0.55Ω
Testing Limit (80%)
0.44Ω
Ia (0.4s)
400A

About MCB Type B

Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.

Typical Circuits for 80A Type B MCB

Recommended cable sizes for 80A Type B MCB circuits
CircuitCable SizeNotes
Sub-main distribution25mm² SWACommercial sub-board feed

Worked Example: Maximum Cable Run for 80A MCB Type B

  1. Maximum Zs (tabulated) = 0.55Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.55 × 0.8 = 0.44Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.44 − 0.8 = —Ω
  5. Using 25mm² T&E: R1+R2 = 1.47 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s and 5s Disconnection — Same Values for Type B

For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 0.55Ω for both disconnection times at 80A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).

80A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.55Ω0.44Ω
MCB Type C0.27Ω0.22Ω
MCB Type D0.14Ω0.11Ω
BS 88 Fuse0.42Ω0.34Ω

Frequently Asked Questions