Max Zs for 100A Type B MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.44Ω

Testing Limit

0.35Ω

Max Zs (5s)

0.44Ω

Ia (0.4s)

500A

At a Glance

Device
MCB Type B100A
Standard
BS EN 60898
Max Zs (0.4s)
0.44Ω
Max Zs (5s)
0.44Ω
Testing Limit (80%)
0.35Ω
Ia (0.4s)
500A

About MCB Type B

Type B MCBs have a magnetic trip range of 3–5× rated current (In). They are the standard choice for domestic and light commercial circuits — lighting, socket outlets, and water heating. The relatively low trip multiplier means higher permissible Zs values compared to Type C or D, making them suitable for circuits with longer cable runs.

Typical Circuits for 100A Type B MCB

Recommended cable sizes for 100A Type B MCB circuits
CircuitCable SizeNotes
Main switch / incomer25–35mm² SWAMain distribution board incomer

Worked Example: Maximum Cable Run for 100A MCB Type B

  1. Maximum Zs (tabulated) = 0.44Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.44 × 0.8 = 0.35Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.35 − 0.8 = —Ω
  5. Using 25mm² T&E: R1+R2 = 1.47 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s and 5s Disconnection — Same Values for Type B

For Type B MCBs, the magnetic trip operates at 3–5× In regardless of whether the required time is 0.4s or 5s. The max Zs is 0.44Ω for both disconnection times at 100A. This means the same limit applies whether protecting a final circuit (0.4s) or a distribution circuit (5s).

100A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.44Ω0.35Ω
MCB Type C0.22Ω0.18Ω
MCB Type D0.11Ω0.09Ω
BS 88 Fuse0.34Ω0.27Ω

Frequently Asked Questions