Skip to content

Max Zs for 100A Type C MCB

BS 7671 Table 41.3 — BS 7671:2018+A2:2022

Max Zs (0.4s)

0.22Ω

Testing Limit

0.18Ω

Max Zs (5s)

0.44Ω

Ia (0.4s)

1000A

At a Glance

Device
MCB Type C100A
Standard
BS EN 60898
Max Zs (0.4s)
0.22Ω
Max Zs (5s)
0.44Ω
Testing Limit (80%)
0.18Ω
Ia (0.4s)
1000A

About MCB Type C

Type C MCBs trip magnetically at 5–10× In. They are designed for circuits with moderate inrush current — motor-driven equipment, air conditioning, and discharge lighting. The higher trip multiplier means lower maximum Zs values, so circuit impedance must be kept tighter than with Type B devices.

Worked Example: Maximum Cable Run for 100A MCB Type C

  1. Maximum Zs (tabulated) = 0.22Ω (BS 7671 Table 41.3)
  2. Testing limit (80%) = 0.22 × 0.8 = 0.18Ω
  3. Assume Ze = 0.8Ω (typical TN-S supply)
  4. Maximum R1+R2 = 0.18 − 0.8 = —Ω
  5. Using 25mm² T&E: R1+R2 = 1.47 mΩ/m
  6. The available R1+R2 margin is insufficient for standard cable — verify the earthing arrangement.

The tight Zs limit for this device means cable runs must be very short. Verify the supply earthing type and consider whether a lower-rated or different device type is more appropriate.

0.4s vs 5s Disconnection — Different Values for Type C

Type C MCBs require 10× In for 0.4s disconnection but only 5× In for 5s. At 100A: max Zs = 0.22Ω (0.4s) vs 0.44Ω (5s). For distribution circuits (5s allowed), you have nearly double the impedance budget. Final circuits serving socket outlets must still meet the 0.4s limit.

Disconnection TimeMax ZsTesting Limit (80%)
0.4 seconds0.22Ω0.18Ω
5 seconds0.44Ω0.35Ω

100A Across Device Types

Device TypeMax Zs (0.4s)Testing Limit
MCB Type B0.44Ω0.35Ω
MCB Type C0.22Ω0.18Ω
MCB Type D0.11Ω0.09Ω
BS 88 Fuse0.34Ω0.27Ω

Frequently Asked Questions

Built by Taro Schenker · Need a website for your trade business? Get in touch